Table 3- 11
S7-200
event
number
10
11
21
22
3.6

Wizards

Note
STEP 7-Micro/WIN wizard generated program code is not converted
This includes subroutines, interrupt routines, V memory data, and symbol definitions. You
must create substitute program logic.
Table 3- 12
STEP 7-Micro/WIN programming wizard code conversion issues
STEP 7-
S7-1200 equivalent
Micro/WIN
feature
Wizard name
AS-i
Planned for the future
Data Log
Under development for
V11 release
EM 241 Modem/
Under development for
Remote Modem
V11 release
EM 253 Position Different programming
method available
Ethernet
Different programming
method available
High-Speed
Different programming
Counter
method available
SIMATIC S7-200 to SIMATIC S7-1200 software conversion tool
Manual, 1/2010
Conversion of S7-200 lowest interrupt priority (timed)
S7-200 Interrupt event
Timed interrupt 0
Timed interrupt 1
Timer T32, CT=PT interrupt
Timer T96, CT=PT interrupt
S7-1200 programming
The current S7-1200 CPU does not support AS-i communication.
A data log function is not supported in the STEP 7 Basic V10.5 SP2.
The S7-1200 CPU does not support a modem expansion module. Also, the
modem and remote modem function are not supported from the S7-1200 RS-
232 module.
The S7-1200 CPU does not support a position expansion module. The S7-
1200 CPU position function is supported as defined by the PLCopen standard.
You must rewrite this program section using the STEP 7 Basic Axis
technology object.
The S7-1200 CPU does not support an Ethernet expansion module. However,
you may convert the module addressing configuration (IP, subnet, gateway).
This address can be used as the default address of the S7-1200 CPU
Ethernet port.
The STEP 7-Micro/WIN HSC wizard generates unprotected (visible in the
editor) interrupt routines and associated code. You were required to add your
own instructions within these interrupt routines. The interrupt routines contain
both wizard generated and manually added code. You must replace the
initialization instructions that use HSC SM memory. Replace the HSC, and
HDEF instructions with the corresponding S7-1200 CPU HSC device
configuration and CTRL_HSC instructions.
Program structure conversion
S7-1200 Interrupt OB conversion result
OB_Cyclic interrupt
(with 100 ms scan time interval)
OB_Cyclic interrupt_1
(with 100 ms scan time interval)
Hardware interrupt OB
Hardware interrupt OB
3.6 Wizards
21