Siemens SIMATIC S7-200 Manual page 17

Software conversion tool
Hide thumbs Also See for SIMATIC S7-200:
Table of Contents

Advertisement

STEP 7-Micro/WIN
Program element
Timers
Counters
High Speed Counter
Table 3- 4
STEP 7-Micro/WIN
Program element
Special Memory
(System status and control)
SCR (Sequence Control Relay)
Accumulators
Indirect Addressing
Analog value address conversion
S7-1200 analog addresses are set during the STEP 7 Basic device configuration. These
addresses are configured as part of the analog I/O device configuration. Analog value
addressing in the S7-1200 uses I and Q memory addresses. The following table lists the
default address ranges that are assigned to analog values converted from a STEP 7-
Micro/WIN program. You must configure the S7-1200 analog I/O to use these addresses or
substitute other addresses.
Table 3- 5
Analog I/O
Analog Input 1
Analog Input 2
Analog Input 3 and following
Analog Output 1 and following
SIMATIC S7-200 to SIMATIC S7-1200 software conversion tool
Manual, 1/2010
S7-200 address
T32
C10
HC0
S7-200 memory addresses that are not converted
S7-200 address
SM0.0
S0.0
AC0
*VD0, *AC0, *LD0
&VB0
S7-200 to S7-1200 analog address conversion
S7-200 Analog address
Program structure conversion
Converted S7-1200 memory address
S7-200 timer symbol names are converted to
S7-1200 timer DB names. S7-200 timer
output bit addresses are converted to a Q bit
address, in the timer DB.
If a S7-200 timer PT (Preset Time) input is a
WORD constant, then the program value is
not converted, for example "100" for PT on
T32 means 100ms. You must convert the S7-
200 program value to the equivalent S7-1200
TIME data format, for example "T#100ms",
"T#59s999ms", or "T# 23h59s999ms".
S7-200 counter symbol names are converted
to S7-1200 counter DB names. S7-200
counter output bit addresses are converted to
a Q bit address, in the counter DB.
ID1000 (Input Double Word 1000)
Converted S7-1200 memory address
Undefined parameter in the program logic:
You must assign a new symbol name and
address in a S7-1200 tag group or data block.
S7-1200 Analog address
AIW0
AIW2
AIW4...
AQW0...
3.2 Memory addresses
IW64
IW66
IW500...
QW500...
17