2) HEATING CAPACITY
Service Ref.
PMH-P1.6BA
PMH-P2BA
Note CA : Capacity (W)
P.C. : Power consumption (kW)
Above data based on indicated voltage
Indoor unit
: 1 phase 230V 50Hz
Outdoor unit : 1 phase 230V 50Hz / 3 phase 400V 50Hz
Cooling capacity correction factors
Service Ref.
5m
PMH-P1.6BA
1.00
PMH-P2BA
1.00
Heating capacity correction factors
Service Ref.
5m
PMH-P1.6BA
1.00
PMH-P2BA
1.00
Indoor
intake
-10
air
D.B.(°C)
CA
P.C.
15
3143
0.97
20
3020
1.05
25
2921
1.12
15
3937
1.40
20
3782
1.52
25
3658
1.61
Refrigerant piping length (no way)
10m
15m
20m
0.993
0.984
0.978
0.993
0.984
0.978
Refrigerant piping length (no way)
10m
15m
20m
0.998
0.995
0.993
0.998
0.995
0.993
Outdoor intake air W.B.(°C)
-5
0
CA
P.C.
CA
P.C.
3416
1.07
3812
1.23
3267
1.15
3614
1.33
3168
1.25
3465
1.44
4278
1.54
4774
1.78
4092
1.66
4526
1.92
3968
1.80
4340
2.09
25m
30m
0.969
0.961
0.969
0.961
25m
30m
0.990
0.988
0.990
0.988
14
5
10
CA
P.C.
CA
P.C.
5000
1.48
5643
1.64
4826
1.59
5445
1.77
4554
1.69
5247
1.89
6262
2.13
7068
2.37
6045
2.30
6820
2.56
5704
2.44
6572
2.74
35m
40m
45m
0.956
0.948
—
0.956
0.948
—
35m
40m
45m
0.985
0.983
—
0.985
0.983
—
15
CA
P.C.
6287
1.77
6064
1.90
5841
2.04
7874
2.56
7595
2.75
7316
2.95
50m
—
—
50m
—
—