6. Protection recommendations

For safety reasons, an RCD (Residual Current Device) and an MCB (Main Circuit Breaker) should be installed.
It should follow the local national low voltage technical requirements.
We recommend for the mains protection consumption:
63A configuration
RCD (63A, 300mA)
MCB of 63 A.
We recommend to installation for every charger RCD and MCB protections as follow:
RCD type A (32 A, 30 mA)
Single phase
MCB of 40A / 32A.
RCD type B (32 A, 30 mA)
Three-
phase
MCB of 40A / 32A.
If the charger is outside a surge protector should be installed.
WBPS-IM-001-EN
CABLE
none
none
none
CAN_H
CAN_L
150A Configuration
RCD (150A, 300mA)
MCB of 150 A.
Pulsar (Connector P2)
PIN
CABLE
PIN 1
none
PIN 2
none
PIN 3
none
PIN 4
CAN_L
PIN 5
CAN_H
8/9