Installation - Digital Control Wiring

1. Ensure the control installation is within the following application and
operating parameters:
• Ambient temperature from 38° to 125°F.
• Relative humidity ranging from 20% to 90% (non-condensing).
• Boiler load rating up to 15A resistive, 1/4hp inductive @ 120VAC.
• Circulator load rating up to 15A, 1/4hp inductive @ 120VAC.
• Space heating load rating up to 8A @ 120VAC.

Oil Burner Controls

ZR Input Terminal
POWER
BURNER
PUMP
PRIORITY
C1
L2
L1
ZR
C2
BOILERMATE
CIRCULATOR

Gas Valve Controls

24 Volt
POWER
BURNER
PUMP
PRIORITY
Z
C1
L2
L1
B
W
C2
BOILERMATE
CIRCULATOR
Other Applications
Multi-Zone Control: Using Post Purge
POWER
BURNER
PUMP
PRIORITY
BOILERMATE
CIRCULATOR
L2
L1
DHW ZONE
X
X
TO BOILER
Note: if your application is not shown, contact AMTROL Technical Support at 401.535.1216.
High Limit (B Terminal)
POWER
L2
L1
HEATING
CIRCULATOR
POWER
L2
L1
HEATING
CIRCULATOR
Multi-Zone Control: No Post Purge
POWER
BURNER
PUMP
PRIORITY
24 OR 120VAC
L2
L1
DHW ZONE
X
X
TO BOILER
BOILERMATE
CIRCULATOR
OR ZONE VALVE
NOTE: Line-voltage and safety-circuit wiring that is external to the
water heater jacket when all panels are in place, and which is part of
the appliance, shall be protected by metal conduit, metal-clad cable or
raceways. Thermoelectric wiring shall be exempt from this provision.
NOTE: Strain relief shall be provided for all conductors leaving an
enclosure. For low-voltage wiring, strain relief at the point of exit from an
enclosure is not necessary if, by wire location or support, protection is
provided against accidental strain.
BURNER
PUMP
PRIORITY
C1
B
C2
BOILERMATE
HEATING
CIRCULATOR
CIRCULATOR
Millivolt
BURNER
PUMP
PRIORITY
C1
B2
B
C2
Z
W
BOILERMATE
HEATING
CIRCULATOR
CIRCULATOR
Outdoor Reset/Automatic Temperature Control
POWER
BURNER
PUMP
L2
L1
ZC
ZR
ZONE/INDRIECT SWITCH
(IF EQUIPPED)
SELECT "INDIRECT"
-6-
Triple-Aquastat
POWER
BURNER
PUMP
L2
L1
R
B
BOILERMATE
CIRCULATOR
Self-Generating
POWER
BURNER
PUMP
L2
L1
B2
B
BOILERMATE
CIRCULATOR
4-Wire Zone Valve
PRIORITY
POWER
BURNER
BOILERMATE
®
CIRCULATOR
24VAC
Z
TRANSFORMER
I
L2
L1
PRIORITY
C1
C2
HEATING
CIRCULATOR
PRIORITY
C1
C2
HEATING
CIRCULATOR
PUMP
PRIORITY
MOTOR
ZONE VALVE
END
SWITCH