ELEVATION SERIES CIM CUBER
FAN MOTOR
Fan Motor
Operation
The Fan Motor (Self Contained Air Cooled
Units) is Mounted to the Fan Shroud covering
the Condenser at the rear of the unit. It is
energized by Relay 1 and controlled by the
Fan Cycling Switch. The Switch should close at
250 psi of head pressure and power the
Motor. The Fan Cycle Switch should open at
200 psi of head and the Fan Motor will de‐
energize.
Troubleshooting
When the Fan Motor is inoperable or cycling outside of the operational parameters, first verify
the LED for Relay 1 is illuminated, indicating the Board is calling for the Fan Motor to run. If the
unit is in the Freeze Cycle and the LED is not illuminated, the issue may be the board. If it is illu‐
minated, check voltage between the Violet and Blue with a meter. Line voltage should be
shown. If inappropriate voltage is shown, verify Molex connection at the Board and correct if
loose. If still no voltage out, replace the Board. If voltage is verified, check contacts of Fan Cycle
Switch for voltage then check contacts which should be closed at pressures above 250 psi. If
open in these conditions, jump control. If Fan Motor comes on, issue is Fan Cycling Control. If
Motor does not come on, check connection at Motor. If verified, the issue is the Fan Motor.
Relay 1LED
R3
R4
R6
R1
R2
R5
Fan
L2/N
Fan Cycle Control
53