Dip Switches And Their Function - Emerson FreezeAlarm FA-I-CCA User Manual

Table of Contents

Advertisement

telephone company and is usually not affected if power is out at the monitored
location.
1.5 Dip Switches and Their Functions:
There are seven dip switches on the back of the unit. They are set at the factory for
the most common installations, but this section describes the feature of each dip
switch should you wish to change any of these functions.
2. DO NOT plug in any components or battery until directed to do so in the
manual.
3. Make sure the toggle switch on the front of the FreezeAlarm is on the
STANDBY position for programming. The ALARM light on the front of the
unit will flash when in STANDBY mode.
4. Select the dip switch options per the Dip Switch Menu found below.
5. Ignore the ON or OFF labels on the dip switches themselves. Use only the
following table for proper explanation of each dip switch setting. UP means
the switch should be pointing towards the top of the FreezeAlarm case and
DOWN means the switch should be pointed towards the bottom of the case.
All the switches should come from the factory in the DOWN position.
Dip Switch Menu
#
Pulse or Tone Dial Out. Select for Pulse Dialing
only if you do not have Touch-Tone™ dialing
1
capability at the monitored location.
Power Alarm Monitoring – you can turn this feature
off or on with this switch. If you do not wish to ever
2
receive an alarm phone call related to a power
failure, put switch in the UP position.
Call Out Frequency. When the FreezeAlarm goes
into alarm mode and begins calling out, it will call
the three programmed phone numbers. If no one has
3
canceled the alarm call-out, it will begin the
sequence again in either 15 minutes or in 2 hours
according to the setting selected.
10 or 3 Ring Call-Out. If the FreezeAlarm received
no answer when calling a phone number, this switch
determines how many times the phone should ring
before the FreezeAlarm hangs up the call and
moves on to the next programmed number. This
saves on long distance charges. Select the 3 ring
option and, if the FreezeAlarm is calling an
4
answering machine set to answer on 4 or more
rings, the FreezeAlarm will hang up before the
answering machine answers, saving on any long
distance charge. This may not work in all areas as
some telephone companies may still charge for an
attempted long distance call which does not go
through.
Description
Settings
UP =
pulse dialing
UP =
Power alarm
Power alarm
monitoring is
monitoring is
OFF
UP =
2 hour call
out frequency
UP =
3 rings
DOWN =
tone dialing
DOWN =
ON
DOWN =
15 minute
call out
frequency
DOWN =
10 rings
7