  • Page 2 - ENGLISH - INTRODUCTION Thank you for choosing our product. The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance. This manual contains detailed instructions on how to install and use the product. It should be kept with care near the NetMan Plus, so that it can be consulted for information on how to use and make the most of your device.
  • Page 3 - ENGLISH - ENVIRONMENTAL PROTECTION In the development of its products, the company devotes abundant resources to analysing the environmental aspects. All our products pursue the objectives defined in the environmental management system developed by the company in compliance with applicable standards. No hazardous materials such as CFCs, HCFCs or asbestos are used in this product.
  • Page 4 - ENGLISH - CONTENTS PRESENTATION __________________________________________________ 6 __________________________________________________________ 6 ESCRIPTION __________________________ 7 PENING THE PACKAGING AND CHECKING THE CONTENTS ________________________________________________________ 8 ETWORK PORT -USB __________________________________________ 8 ICRO COMMUNICATION PORT _____________________________________________________ 8 ETWORK SERVICES SSH _____________________________________________________________________ 8 Serial network ____________________________________________________________ 8 Wake-on-LAN _____________________________________________________________ 8 HTTP ____________________________________________________________________ 9 SNMP ___________________________________________________________________ 9...
  • Page 5 - ENGLISH - Scheduled NTP menu _____________________________________________________ 24 UPS config menu ________________________________________________________ 25 Services 1 menu _________________________________________________________ 26 SNMPv1 config menu _____________________________________________________ 27 SNMPv1 community menu _________________________________________________ 27 Email config menu _______________________________________________________ 28 Email logic menu _________________________________________________________ 29 Miscellaneous menu ______________________________________________________ 30 Activation 1 menu ________________________________________________________ 31 Services 2 menu _________________________________________________________ 31 Wake-On-LAN address menu _______________________________________________ 32...
  • Page 6: Presentation

    PRESENTATION ESCRIPTION NetMan 202 plus is a device that allows UPS management through a LAN (Local Area Network); the accessory supports all the main network protocols (SNMP v1 and v3, TCP/IP, HTTP and so on) and is compatible with Ethernet 10/100Mbps IPv4/6 networks. The UPS can therefore be integrated easily into medium and large-sized networks.
  • Page 7: O Pening The Packaging And Checking The Contents

    - ENGLISH - PENING THE PACKAGING AND CHECKING THE CONTENTS After opening the packaging, first check the contents. The packaging should contain: NetMan 202 plus USB cable - 7 -...
  • Page 8: N Etwork Port

    - ENGLISH - ETWORK PORT NetMan plus connects to 10/100 Mbps Ethernet networks by means of connector RJ45 (see paragraph “Specifications for the cabling of the network cable”). The LEDs built into the connector describe the status of the network: ...
  • Page 9: Http

    - ENGLISH - HTTP Using the HTTP (Hyper Text Transfer Protocol), is possible to configure the NetMan plus and the status of the UPS can be monitored by means of a web browser without having to install additional software (see paragraph “Monitoring with HTTP”). All the most popular web browsers are supported.
  • Page 10 - ENGLISH - FTP (File Transfer Protocol) is a network protocol used for file exchange. NetMan plus uses this protocol for two purposes: 1. download of files of the UPS values and events history log archive (Datalog and Eventlog) with user “user” 2.
  • Page 11: Email

    - ENGLISH - Email NetMan plus can send a notification e-mail if one or more alarm conditions occur. The e-mails can be sent to up to three recipients and they can be sent for seven different kinds of alarm. SMTP (Simple Mail Transfer Protocol) is the protocol used to send the e-mails. They are sent to an SMTP server on port 25.
  • Page 12: Reports

    - ENGLISH - Reports NetMan plus can send periodic e-mails with an attachment containing the files of the UPS values and events history log archive. This service can be used to periodically save the history log archives. The “Email” service must be enabled in order to send reports; the reports are sent to all the addresses configured for this service (for more details see paragraph “Configuration”).
  • Page 13: Ups Values And Events History Log Archive

    - ENGLISH - VALUES AND EVENTS HISTORY LOG ARCHIVE NetMan plus records the UPS values (Datalog) and events (Eventlog) in a history log archive. The data are saved to file in text format and can be read either by means of an electronic spreadsheet (which allows the data to be ordered chronologically) or by any text editor.
  • Page 14: Datalog

    - ENGLISH - Datalog The Datalog service records the main UPS data in the ‘data.log’ file. The file can be downloaded via FTP or can be sent by e-mail using the “Email report” service. The following data are monitored:  Input voltage line 1 ...
  • Page 15: Available Sensors

    - ENGLISH - NVIRONMENTAL SENSORS OPTIONAL Is possibile to connect to NetMan plus the environmental sensors for monitoring temperature, humidity and digital input/output. The information provided by these sensors can be showed with the UPS monitoring and control software or with a web browser (the HTTP service must be active). The values provided by the sensors may also be requested with SNMP according to the RFC 3433 standard.
  • Page 16: Installation And Configuration

    PLUS Remove the cover of the UPS expansion slot by removing the two retaining screws. Insert NetMan 202 plus in the slot. Connect the device to the network by means of connector RJ-45 (see “Specifications for the cabling of the network cable”) Secure Netman in the slot using the two screws removed previously.
  • Page 17: Saving The Configuration And Applying The Changes

    (see paragraph “Menu Save and load”). The clock settings (see paragraph “Time settings Menu”) become effective without saving. Users It is possible to access to NetMan 202 plus with various users:  admin (password admin): user with right to modify the configuration ...
  • Page 18: Main Configuration Menu

    - ENGLISH - Main configuration menu The main configuration menu displays a screen like the following: /------------------------/ NetMan plus /------------------------/ config..:<-- Time setting...: UPS config..: Services 1..: Services 2..: Security..: Save and load..: Press [Esc] to quit Data from flash - On Line From this main menu it is possible to access the various submenus, the function of each of which is shown in the table below.
  • Page 19 - ENGLISH - To move within this menu and the following menus, use the keys as described in the following table; the arrow or the cursor shows the current selection. Function Direction keys To move the cursor within the menus (Arrow up, down, right, left) Goes on to next option Choice of submenu...
  • Page 20 - ENGLISH - Here is a graphical rapresentation of the menus and submenus: - 20 -...
  • Page 21: Ip Config Menu

    - ENGLISH - IP config menu /------------------------/ IP config /------------------------/ Hostname..:ups_server address/DHCP:dhcp Netmask..: Gateway..: Primary DNS..: Secondary DNS..: Mailhost..: With this menu the main network parameters can be set as described in the following table. Field Parameters to be inserted Hostname Enter the NetMan plus host name Enter the IP address for a static IP;...
  • Page 22: Time Setting Menu

    - ENGLISH - After pressing “ESC” and “Y” to confirm exit from the menu, a screen is displayed summarizing the current settings (see image below). Press the “ENTER” key to return to the main menu. The configuration must however be saved to make it effective after restart of the device (see “Save and load”...
  • Page 23 - ENGLISH - Pressing the “ENTER” key corresponding to the “Set time” command displays a screen like the one shown below. Current date is Wed Jun 15 08:09:40 GMT 2005 Insert new date and clock time in this form: MMDDYYYYHHMMSS 06152005081000 Current date is Wed Jun 15 08:10:00 GMT 2005 Enter the date and time in the format shown, then press the ENTER key and then “ESC”...
  • Page 24: Scheduled Ntp Menu

    - ENGLISH - Scheduled NTP menu /------------------------/ Scheduled NTP /------------------------/ server..:time_server Sync only at...:13 hour (0 - 23) Sync only at...:* day of week (0 - 6) (Sunday=0 or 7) OR sun,mon,tue ... Sync only at...:1 day of month (1 - 31) Insert * where the value is not needed.
  • Page 25: Ups Config Menu

    - ENGLISH - UPS config menu /------------------------/ UPS config /------------------------/ PRTK Code..:GPSER11201XX Name...:ups3 Address..:1 Serial number..:324321 With this menu the UPS parameters must be set as described in the following table, for the UPS to be able to communicate correctly with the device. Field Parameters to be inserted PRTK Code...
  • Page 26: Services 1 Menu

    - ENGLISH - Services 1 menu /------------------------/ Services 1 /------------------------/ SNMP config..:<-- SNMP community.: Email config...: Email logic..: Miscellaneous..: Activation 1...: With this menu the configuration screens of the various services can be accessed as described in the following table. Menu Function SNMP config...
  • Page 27: Snmpv1 Config Menu

    - ENGLISH - SNMPv1 config menu /------------------------/ SNMPV1 config /------------------------/ Trap receiver 1:powernetguard Trap receiver 2:192.168.5.96 Trap receiver 3: Trap receiver 4: Trap receiver 5: Trap receiver 6: Trap receiver 7: With this menu the IP addresses to which traps are sent can be configured. Traps are SNMP messages that are sent to an SNMP manager for alarm notification.
  • Page 28: Email Config Menu

    - ENGLISH - Email config menu /------------------------/ Email config /------------------------/ Email address 1:myself@mycompany.com Email address 2:service@service.com Email address 3:anotheremail@mycompany.com Sender address.:NetMan_plus Customer..:MyCustomer Report interval:01-05:10 DD-HH:MM User name..:User 1 Password..:Password This menu may be used to configure the addresses to which to send the alarm notification and report e-mails and other parameters of the e-mail service as described in the following table.
  • Page 29: Email Logic Menu

    - ENGLISH - Email logic menu /------------------------/ Email logic /------------------------/ Email 1 Email 2 Email 3 Logic: UPS Lock..: X<-- Ovrload/Ovrtemp: UPS Failure..: On bypass..: Battery work...: Battery low..: Communic lost..: With this menu it can be established to which addresses the e-mails will be sent when certain events occurs.
  • Page 30: Miscellaneous Menu

    - ENGLISH - Miscellaneous menu /------------------------/ Miscellaneous /------------------------/ frequency..:5 Port..:33000 sysContact..:Administrator sysName..:My Server sysLocation..:new building With this menu further device parameters can be configured as described in the following table. Field Parameters to be inserted Enter the delay, measured in seconds, between one data log and the next Log frequency (see paragraph “Datalog”) UDP Port...
  • Page 31: Activation 1 Menu

    - ENGLISH - Activation 1 menu /------------------------/ Activation 1 /------------------------/ Enable telnet..:[ON/off]<-- Enable FTP..:[ON/off] Enable HTTP..:[ON/off] Enable DataLog.:[ON/off] Enable Modem Tx:[on/OFF] Enable Modem Rx:[on/OFF] Enable SNMP..:[ON/off] Enable Email...:[ON/off] Enable UDP..:[ON/off] Enable Report..:[ON/off] With this menu the services implemented in NetMan plus can be activated or deactivated: Use the ENTER key to change the selected configuration (“ON”...
  • Page 32: Wake-On-Lan Address Menu

    - ENGLISH - Wake-On-LAN address menu /------------------------/ Wake-on-LAN address /------------------------/ MAC Address 1..:00-12-3F-2B-F6-6F MAC Address 2..:aa-bb-cc-dd-ee-ff MAC Address 3..:00-00-00-00-00-00 MAC Address 4..: MAC Address 5..: MAC Address 6..: MAC Address 7..: MAC Address 8..: With this menu is possible to insert up to 8 MAC address to execute Wake-on-LAN. Please make sure that your PC supports this function, and that it is correctly configured.
  • Page 33: Activation 2 Menu

    - ENGLISH - Activation 2 menu /------------------------/ Activation 2 /------------------------/ Enable Serial N:[ON/off]<-- Enable Sensors.:[ON/off] Enable WOL :[on/OFF] With this menu the services implemented in NetMan plus can be activated or deactivated: Use the ENTER key to change the selected configuration (“ON” or “OFF”). ...
  • Page 34 - ENGLISH - Example: how to connect a Temperature sensor, a Humidity & Temperature sensor and a Digital I/O & Temperature sensor in exactly this order. Sensors Devices Press [C] to change sensors, [E] to exit Connect the first sensor (Temperature), and press “Y”. Sensors Devices [1] Sensor Temperature (F100000013BE0628) + Temperature...
  • Page 35: I/O Sensors Menu

    - ENGLISH - I/O Sensors menu /------------------------/ Output /------------------------/ UPS Lock..: -<-- Ovrload/Ovrtemp: UPS Failure..: On bypass..: Battery work...: Battery low..: Communic lost..: Input sensor...: Press [Esc] to quit With this menu is possibile to associate a digital output of the installed sensors to one or more events of the UPS.
  • Page 36: Threshold Sens Menu

    - ENGLISH - Threshold sens menu /------------------------/ Threshold sens /------------------------/ Temperature max:100 degree C Temperature min:20 degree C Temp hysteresis:5 degree C Humidity Max...:100 % RH Humidity Min...:0 % RH hysteresis.:5 % RH Press [Esc] to quit With this menu is possible to set the alarm threshold for humidity and temperature sensors. When exceeding the threshold, a SNMP alarm trap is sent.
  • Page 37: Security Menu

    - ENGLISH - Security menu /------------------------/ Security /------------------------/ Password...:<-- Firewall..: From this menu the setup password, the UDP password and the firewall can be configured as described in the following table. Menu Function UDP Password To change the password used for UDP/UPSMon communication Firewall To configure access from the network default configuration: “password”...
  • Page 38 - ENGLISH - Pressing the ENTER key corresponding to the “Firewall” command displays a screen like the one shown below. /------------------------/ Firewall /------------------------/ Access IP 1..:*.*.*.* Access IP 2..:0.0.0.0 Access IP 3..:0.0.0.0 Access IP 4..:0.0.0.0 Access IP 5..:0.0.0.0 Access IP 6..:0.0.0.0 Access IP 7..:0.0.0.0...
  • Page 39: Save And Load Menu

    - ENGLISH - Save and load menu /------------------------/ Save and load /------------------------/ Apply changes..:<-- Revert changes.: Reset default..: With this menu the configuration can be saved to make it effective or to load other configurations as described in the following table. Function Description Saves the configuration in flash memory and then automatically restarts to...
  • Page 40 FTP with user “admin” (default password is “admin”). If this file is not present, SNMPv1 will be used. Each line of the file is parsed by netman 202 plus and must begin with one of these keyword: ...
  • Page 41 - ENGLISH - <securityType> is the minimum security level that must be used to gain access to this access right. Possible values are:  noauthnopriv (no authentication and no privacy)  authnopriv (authentication but no privacy)  authpriv (authentication and privacy) <contextMatch>...
  • Page 42 - ENGLISH - A sample snmp.conf is provided; the default users authorized are: Name unsecureUs MD5DES SHADES Auth Noauth protoc Priv nopriv nopriv nopriv protoc Auth MD5UserAuthPassw SHAUserAuthPassw MD5DESUserAuthPassw SHADESUserAuthPassw passwo Priv MD5DESUserPrivPassw SHADESUserPrivPassw passwo The SNMP agent will send SNMPv3 trap to address 10.2.10.1. - 42 -...
  • Page 43: Configuration Of Several Devices

    - ENGLISH - Configuration of several devices If several devices requiring similar configuration parameters are to be installed, configure the first card, connect via FTP with the admin user, download the configuration file, and upload them on all devices to be configured via FTP. Example of FTP connection for multiple installations HTTP ONITORING WITH...
  • Page 44: View Http

    - ENGLISH - View HTTP It is possible to view the status of the UPS without entering the login by pressing “View”. By pressing “View”, a screen like the one shown below will be displayed, with the main UPS operating data. - 44 -...
  • Page 45: Setup Http

    - ENGLISH - Besides the “Main” view, is possible to switch the view from the “Status” menu which includes also the “Nominal” view and the “Sensor” view (for viewing external sensors). It is also possible to download the event.log and data.log (if available) from the “Log” menu. Setup HTTP For configuration it will be requested to enter the log in and password.
  • Page 46 - ENGLISH - The settings are the same of ssh config. The user is logged out after 3 minutes of inactivity, or when the “Logout” is selected. By pressing submit the data for the current view is sent to the netman; by pressing reset the data for the current view is discarded.
  • Page 47 - ENGLISH - Example of display via HTTP The following buttons are found on the left-hand side of the page:  Nominal Data: opens a page displaying the nominal values of the UPS, the list of active alarms and a diagram of UPS operation (see image on next page) ...
  • Page 48 - ENGLISH - TCP/IP ODBUS PROTOCOL This service is always active on the TCP port 502. The supported function are listed below, together with the accessible registers. UPPORTED FUNCTION SUPPORTED ACCESSIBLE DATA FUNCTION DESCRIPTION FUNCTION AREA (0x01) STATES BIT READING (0x02) STATES (0x03)
  • Page 49 - ENGLISH - UPS: T ABLES OF STATES MEASUREMENTS NOMINAL DATA AND COMMANDS REGISTER UPS - STATES NUMBER ADDRESS NUMBER ADDRESS Test in progress[0=No / 1=YES] Shutdown active [0=No / 1= YES] Battery charged[0=No / 1= YES] Battery charging[0=No / 1= YES] Bypass bad[0=No / 1= YES] Normal operation[0=No / 1= YES] On bypass[0=No / 1= YES]...
  • Page 50 - ENGLISH - Output current phase L2 0.1*A Output current phase L3 0.1*A Output peak current phase L1 0.1*A Output peak current phase L2 0.1*A Output peak current phase L3 0.1*A Load phase L1 Load phase L2 Load phase L3 Output active power phase L1 0.1 kW Output active power phase L2...
  • Page 51 - ENGLISH - REGISTER UPS – NOMINAL DATA UNIT NUMBER ADDRESS 7377 7276 Output nominal voltage (star) Output nominal frequency 0.1*Hz Output nominal power 100*VA 8183 8082 Battery nominal capacity (battery expansion included) Battery benches (1 or 2) Battery type Integer 87112 86111...
  • Page 52 - ENGLISH - REGISTER SPECIAL FLAGS (SENTR UPS) UNIT NUMBER ADDRESS Byte 1 of “s = xx..” code / Byte 2 of “s = ..xx” code Flag Byte 1 of “c = xx..” code / Byte 2 of “c = ..xx” code Flag Byte 1 of “b = xx..”...
  • Page 53: F Irmware Update

    - ENGLISH - IRMWARE UPDATE The NetMan 202 plus firmware can be updated via FTP. Connect via FTP with the user “fwupgrade” (password “fwupgrade”) and copy the updated firmware. Then restart the card, by pressing the reset button or via SSH enter into the menu with user "admin"...
  • Page 54: Technical Data

    2   2 3   3 6   6 Pins 1 and 2 must be connected to one twisted pair, pins 3 and 6 to another. ECHNICAL SPECIFICATIONS NetMan 202 plus Input voltage [Vdc] POWER SUPPLY Maximum input current...
  • Page 55 0MNACCSA3ENUC...