Commissioning - Honeywell Sensepoint XCL Installation Manual

Fixed gas detector
Hide thumbs Also See for Sensepoint XCL:
Table of Contents

Advertisement

3.1 Commissioning the Detector
26
NOTE
The Sensepoint XCL gas detector is supplied from the factory
pre-calibrated. However, it is strongly recommended that the
detector response is checked and if necessary, re-calibrated before
placing it into service. Refer to Calibration on page 34 for details on
the correct calibration procedure.
The following procedure should be followed carefully and only be
performed by suitably-trained personnel.
Chapter

Commissioning

1. Remove the front cover.
a) Pull the flap on the bottom side
to open it.
b) Insert a thin, straight tool, such
as a small screwdriver, into the
hole to the right of the remote
gassing port.
c) Apply slight pressure to the tool,
turn the cover counterclockwise
until it stops. Lift the cover clear
of the electronics module.