ABB
Transformer Protection and Control
RET615
Product version: 4.0
Table 29. Three-phase non-directional overcurrent protection (PHxPTOC) main settings
Parameter
Start Value
Time multiplier
Operate delay time
1)
Operating curve type
1)
For further reference please refer to the Operating characteristics table
Function
PHLPTOC
PHHPTOC
PHIPTOC
PHLPTOC
PHHPTOC
PHLPTOC
PHHPTOC
PHIPTOC
PHLPTOC
PHHPTOC
PHIPTOC
Value (Range)
Step
0.05...5.00 x I
0.01
n
0.10...40.00 x I
0.01
n
1.00...40.00 x I
0.01
n
0.05...15.00
0.01
0.05...15.00
0.01
40...200000 ms
10
40...200000 ms
10
20...200000 ms
10
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15,
17, 18, 19
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
Definite time
1MRS756891 F