ABB RET615 Product Manual page 29

Relion 615 series. transformer protection and control
Hide thumbs Also See for RET615:
Table of Contents

Advertisement

ABB
Transformer Protection and Control
RET615
Product version: 4.0
Table 16. Station communication link, fibre-optic
Connector
Fibre type
LC
MM 62.5/125 or 50/125
μm glass fibre core
ST
MM 62.5/125 or 50/125
μm glass fibre core
1)
(MM) multi-mode fibre, (SM) single-mode fibre
2)
Maximum allowed attenuation caused by connectors and cable together
Table 17. IRIG-B
Description
IRIG time code format
Isolation
Modulation
Logic level
Current consumption
Power consumption
1)
According to 200-04 IRIG -standard
Table 18. Lens sensor and optical fibre for arc protection
Description
Fibre-optic cable including lens
Normal service temperature range of the lens
Maximum service temperature range of the lens, max 1 h
Minimum permissible bending radius of the connection
fibre
Table 19. Degree of protection of flush-mounted IED
Description
Front side
Rear side, connection terminals
1)
Wave length
1300 nm
820-900 nm
Max. distance
Permitted path attenuation
2 km
<8 dB
1 km
<11 dB
Value
1)
B004, B005
500V 1 min.
Unmodulated
TTL Level
2...4 mA
10...20 mW
Value
1.5 m, 3.0 m or 5.0 m
-40...+100°C
+140°C
100 mm
Value
IP 54
IP 20
1MRS756891 F
2)
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents