ABB RET615 Product Manual page 27

Relion 615 series. transformer protection and control
Hide thumbs Also See for RET615:
Table of Contents

Advertisement

ABB
Transformer Protection and Control
RET615
Product version: 4.0
Table 10. RTD/mA measurement (XRGGIO130)
Description
RTD inputs
Supported RTD
sensors
Supported resistance
range
Maximum lead
resistance (three-
wire measurement)
Isolation
Response time
RTD/resistance
sensing current
Operation accuracy
mA inputs
Supported current
range
Current input
impedance
Operation accuracy
Table 11. Signal output X100: SO1
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time constant L/
R<40 ms
Minimum contact load
Value
100 Ω platinum
TCR 0.00385 (DIN 43760)
250 Ω platinum
TCR 0.00385
100 Ω nickel
TCR 0.00618 (DIN 43760)
120 Ω nickel
TCR 0.00618
250 Ω nickel
TCR 0.00618
10 Ω copper
TCR 0.00427
0...2 kΩ
25 Ω per lead
2 kV (inputs to protective earth)
<4 s
Maximum 0.33 mA rms
Resistance
Temperature
± 2.0% or ±1 Ω
±1°C
10 Ω copper: ±2°C
0...20 mA
44 Ω ± 0.1%
±0.5% or ±0.01 mA
Value
250 V AC/DC
5 A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
1MRS756891 F
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents