ABB RET615 Product Manual page 31

Relion 615 series. transformer protection and control
Hide thumbs Also See for RET615:
Table of Contents

Advertisement

ABB
Transformer Protection and Control
RET615
Product version: 4.0
Table 22. Electromagnetic compatibility tests
Description
1 MHz/100 kHz burst disturbance
test:
• Common mode
• Differential mode
3 MHz, 10 MHz and 30 MHz burst
disturbance test:
• Common mode
Electrostatic discharge test:
• Contact discharge
• Air discharge
Radio frequency interference test:
Fast transient disturbance test:
• All ports
Surge immunity test:
• Communication
• Other ports
Power frequency (50 Hz) magnetic
field immunity test:
• Continuous
• 1...3 s
Pulse magnetic field immunity test:
Damped oscillatory magnetic field
immunity test:
• 2 s
• 1 MHz
Type test value
2.5 kV
2.5 kV
2.5 kV
8 kV
15 kV
10 V (rms)
f=150 kHz...80 MHz
10 V/m (rms)
f=80...2700 MHz
10 V/m
f=900 MHz
20 V/m (rms)
f=80...1000 MHz
4 kV
1 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
300 A/m
1000 A/m
1000 A/m
6.4/16 µs
100 A/m
400 transients/s
1MRS756891 F
Reference
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
IEC 61000-4-18
IEC 60255-22-1, class III
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
IEC 61000-4-6
IEC 60255-22-6, class III
IEC 61000-4-3
IEC 60255-22-3, class III
ENV 50204
IEC 60255-22-3, class III
IEEE C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
IEC 61000-4-5
IEC 60255-22-5
IEC 61000-4-8
IEC 61000-4-9
IEC 61000-4-10
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents