Space Heating/Cooling - Daikin ERGA04DAV3A Installer's Reference Manual

Daikin altherma - low temperature split
Hide thumbs Also See for ERGA04DAV3A:
Table of Contents

Advertisement

#
Code
[3.6]
[0-04]
Set weather-dependent cooling:
T t
[0-05]
[0-06]
[0-05]
[0-07]
[0-04]
▪ T
: Target leaving water temperature
t
(additional zone)
▪ T
: Outdoor temperature
a
▪ [0-07]:
temperature. 10°C~25°C
▪ [0-06]:
temperature. 25°C~43°C
▪ [0-05]:
temperature
temperature equals or drops below the
low
[9‑07]°C~[9‑08]°C
Note: This value should be higher
than
temperatures
required.
▪ [0-04]:
temperature
temperature equals or rises above the
high
[9‑07]°C~[9‑08]°C
Note: This value should be lower than
[0‑05]
temperatures colder water is required.
Emitter type
For more info about this functionality, see
page 53.
#
Code
[3.7]
[2‑0D]
Emitter type
▪ 0: Underfloor heating
▪ 1: Fancoil unit
▪ 2: Radiator
The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:
Emitter type
Space heating
Additional zone
setpoint range
[9‑05]~[9‑06]
0: Underfloor heating Maximum 55°C
1: Fancoil unit
Maximum 55°C
2: Radiator
Maximum 65°C
Setpoint range
For more information about this setting, also see
zone" on
page 53.
#
Code
Leaving water temperature range for the additional leaving water
temperature zone (= the leaving water temperature zone with the
highest leaving water temperature in heating operation and the
lowest leaving water temperature in cooling operation)
[3.8.1]
[9-05]
Heating minimum: 15°C~37°C
Final English - Tanslations in progress
ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA
Daikin Altherma – Low temperature split
4P495248-1 – 2017.12
Description
[0-07]
[0-06]
T a
Low
outdoor
ambient
High
outdoor
ambient
Desired
leaving
water
when
the
outdoor
ambient
temperature.
[0‑04]
as
for
low
outdoor
less
cold
water
is
Desired
leaving
water
when
the
outdoor
ambient
temperature.
as
for
high
outdoor
"8.4.3  Main zone"  on
Description
Target delta T in
heating [1‑0C]
Variable (see [2.B])
Variable (see [2.B])
Fixed 10°C
"8.4.3  Main
Description
#
Code
[3.8.2]
[9-06]
Heating maximum
▪ [2‑0D]=2 (emitter type additional zone
= radiator)
37°C~65°C
▪ Else: 37°C~55°C
[3.8.3]
[9-07]
Cooling minimum: 5°C~18°C
[3.8.4]
[9-08]
Cooling maximum: 8°C~22°C
Control
The control type is displayed here, but cannot be adjusted. It is
determined by the control type of the main zone. For more info about
the functionality, see
"8.4.3 Main zone" on
#
Code
[3.9]
N/A
Control
▪ Leaving water if the control type of the
main zone is Leaving water.
▪ External room thermostat if the control
type of the main zone is External room
thermostat or Room thermostat.
Thermostat type
Only applicable in external room thermostat control. For more info
about the functionality, see
"8.4.3 Main zone" on
#
Code
[3.A]
[C‑06]
External room thermostat type for the
additional zone:
▪ 1: 1 contact. Connected to only 1
digital input (X2M/35a)
▪ 2: 2 contacts. Connected to 2 digital
inputs (X2M/34a and X2M/35a)
Leaving water temperature: Delta T
For more information, see
"8.4.3 Main zone" on
#
Code
[3.B.1]
[1-0C]
Delta T heating: A minimum temperature
difference is required for the good
operation of heat emitters in heating
mode.
▪ If [2-0C] = 2, this is fixed to 10°C
▪ Else: 3°C~10°C
[3.B.2]
[1-0E]
Delta T cooling: A minimum temperature
difference is required for the good
operation of heat emitters in cooling
mode.
▪ 3°C~10°C
8.4.5

Space heating/cooling

About space operation modes
Depending on your heat  pump model, you have to tell the system
which space operation mode to use: heating or cooling.
If a ... heat pump
model is installed
Heating/cooling
The system can heat up and cool down a
space. You have to tell the system which
space operation mode to use.
Heating only
The system can heat up a space, but
NOT cool down a space. You do NOT
have to tell the system which space
operation mode to use.
8 Configuration
Description
page 53.
Description
page 53.
Description
page 53.
Description
Then...
Installer reference guide
59