3.6.4 Moving average processing count setting (Address RWwm+2)

3.6.5 CH.
Digital output value ( Address RWrn to RWrn+3 )
(1) Set the average processing count of the channel for which moving average
processing has been specified in the CH.
specifying flag (RYn0 to RYn3).
(2) Sampling processing is performed for the channel whose CH.
processing specifying flag (RYn0 to RYn3) was not turned on, independently of
the moving average processing count setting.
(3) Operation is performed according to the setting made for the leading edges of the
initial data setting request flag (RY(n+1)9).
(4) The default setting is 4 times for all channels.
Bits b2, b3, b6, b7, b10, b11, b14 and b15 are ignored.
b15
b14 b13
b12
CH.4
Ignored
Set Count
4 times
8 times
16 times
32 times
(1) The digital value after the A/D conversion is stored in the remote register address
from RWrn to RWrn+3 for each channel.
(2) The digital output value is expressed in a 16-bit encoded binary.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
b12 to b14 change to 1 when the sign is negative
(1 at b15) and to 0 when it is positive (0 at b15).
(A negative digital value is expressed in 2's complement.)
Sign bit
1: Negative
0: Positive
b11
b10 b9
b8 b7
CH.3
Ignored
Date section
3 - 16
MELSEC-A
moving average processing
moving average
b6
b5
b4
b3
CH.2
Ignored
Ignored
Set Value
0
H
1
H
2
H
3
H
b2
b1
b0
CH.1

Advertisement

Table of Contents
loading

Table of Contents