2.3.3 Antistatic Precautions

As with all modern electronic circuits, the Printed Circuit Boards (PCBs) in Touchpoint Plus systems utilise some static-
sensitive components that can be severely damaged if subjected to static discharge. Static can be generated on the
human body by friction or movement and is discharged through the first contacted route to earth. It can also jump gaps
between items of differing electrical potential.
Static damage is not always immediately apparent and can cause component failure at any time after the static discharge
has occurred. It is, therefore, very important that everyone takes the following precautions when handling PCBs:
An industry approved antistatic wrist strap, containing a resistive component greater than 1Megohm, must be worn
and connected to an effective earth (ground) point. The continuity between the strap and earth (ground) must be
checked regularly.
PCBs must only be handled by their non-conductive edges. Do not allow any components, conductive tracks or
contacts to come into proximity with the body, clothing, machinery, power source or any material other than a static-
dissipative mat.
With the exception of assemblies containing batteries, anti-static packaging must be used for transporting PCBs and
Integrated Circuits (ICs). All Touchpoint Plus electronic components are shipped in appropriate packaging that can be
re-used when returning items for test or repair.
Avoid wearing clothing manufactured from, or containing a high proportion of, man-made fibres. These can build up a
high static potential that may not be discharged through the body or wrist strap.
An effective earth (ground) point is the protective earth (ground) bus bar inside the enclosure. This can be used to connect
a suitable anti-static wrist strap provided that the Gas detection system is connected to protective earth (ground) via the
mains power supply cable.
If installed correctly, the equipment earth (ground) point is connected directly to mains earth (ground) via
protective earth and the mains power supply cable, and the earth (ground) circuit cannot be broken by operating

2.3.4 Good Practice

After switching off the system, it is good practice to wait at least 15 seconds before switching it on again. This allows the
circuits and RAM to discharge adequately before being powered-up again. Failing to do so may cause data corruption.

2.3.5 Lithium Battery Hazard

Lithium batteries are fitted to Touchpoint Plus as backup power sources.
Replace the factory installed battery pack TPPLOIBB with Honeywell Analytics Asia Pacific replacement battery pack part
no. TPPLSIBB and the PCB CMOS battery with type CR2032 only.
Use of other batteries may present a risk of fire or explosion.
Lithium batteries may cause severe injury or death if swallowed, and may catch fire or explode if mishandled,
Always handle lithium batteries with care, keep them out of the reach of children, and dispose of them carefully
MAN0996_Iss 1_02/16
Pt. No. 3011M5044_EN
Safety
the Isolator switch or circuit breaker.
LITHIUM BATTERY TOXIC AND FIRE HAZARDS
recharged, burned or disposed of incorrectly.
in accordance with local regulations.
Batteries shall only be fitted, removed or replaced in non-hazardous (safe) areas.
IMPORTANT