6.2.2 Exercising the Relays

Relay output channels can be tested by forcing the relays to an active state:
1)
Ensure that relay activated output systems (i.e. emergency deluge / sirens etc.) are isolated before starting the test.
2)
Login as an Administrator or Service.
3)
Touch
Menu>System Test>Force Relay
4)
Touch the active (yellow) Relay Output Channels to be tested, and toggle them on.
5)
Check the selected relay output contact power switching using a suitable test tool or voltmeter.
6)
Touch [Finish]>[Cancel] and all selections will turn off.
7)
Proceed to the next step.

6.2.3 Checking the mA Outputs

Milliamp (mA) output channels can be tested by forcing the mA output:
1)
Ensure that relay activated output systems (i.e. emergency deluge / sirens etc.) are isolated before starting the test.
2)
Login as an Administrator or Service.
3)
Touch
Menu>System Test>Force 4-20mA
4)
Touch the All radio button and check the mA output value; touch the mA box to change it. For single channels touch
the Single Channel number box and then scroll through the list and touch the required channel followed by [Select].
MAN0996_Iss 1_02/16
Pt. No. 3011M5044_EN
Maintenance
If the relays are switching mains voltages, hazardous live terminals may be present.
Ensure that all mains current is isolated and dissipated before touching live terminals.
WARNING
.
.