Powerware 8 - 15 kVA User Manual page 40

230v 50/60 hz output (1/3-phase input)
Table of Contents

Advertisement

7.
Turn ON S3 switch to connect UPS output to load:
ON
ON
ON
8.
Turn OFF S1 switch to disconnect bypass output:
OFF
ON
ON
9.
Use LCD to transfer the UPS to normal mode.
10.
Remount the locking plate of the S1-3 swiches to the position to prevent the use of them.
11.
UPS is now in Normal mode, see below:
40
UPS 8 – 15 kVA, 230V 50/60 Hz output
User's Guide
1022403
Revision B1