2. Specification

Model
Power supply
Rated capacity
Rated capacity
Capacity (46°C)
Rated power input
Cooling
Power input (46°C)
Max. power input
EER
Rated current
Max. current
Rated capacity
Rated capacity
Rated power input
Heating
Max. power input
COP
Rated current
Max. current
Brand
Model
Type
Compressor quantity
Capacity
Power Input
Compressor
Rated current(RLA)
Speed
Crankcase Heater
Refrigerant oil brand
Refrigerant oil type
Refrigerant oil charge
Brand
Model
Voltage
IP Class
Type
Insulation class
Outdoor fan motor
Safe class
Power Input
Output
Rated current
Capacitor
Speed
AU042FPERA
Ph/V/Hz
kW
12.60
kBtu/h
42.99
kW
11.2
kW
3.11
kW
3.77
kW
7.20
4.05
A
14.73
A
34.09
kW
14.20
kBtu/h
48.45
kW
3.18
kW
6.9
4.47
A
15.06
A
32.67
Rotary
1 INV
W
13780
W
4130
A
15.8
rps
75
W
33
IDEMITSUKOSAN CO.LTD
FV50S
ml
1100
NIDEC
310V
IP44
DC
E
I
W
180
W
120
A
0.4
μF
/
rpm
900
3
AU052FPERA
1Ph,220-230V,50/60Hz
14.00
47.77
12.6
3.51
4.25
7.50
3.99
16.62
35.51
16.00
54.59
3.72
7.2
4.30
17.61
34.09
MITSUBISHI ELECTRIC
MNB42FFAMC-L
Rotary
1 INV
13780
4130
15.8
80
33
FV50S
1100
NIDEC
SIC-88FWJ-F1180-1
310V
IP44
DC
E
I
180
120
0.4
/
900
AU062FPERA
15.50
52.89
14
4.31
5.22
7.80
3.60
20.41
36.93
18.00
61.42
4.39
7.5
4.10
20.79
35.51
Rotary
1 INV
13780
4130
15.8
85
33
FV50S
1100
NIDEC
310V
IP44
DC
E
I
180
120
0.4
/
900

Hide quick links: