Installation Manual for Outdoor Unit
No. 0150521898
• This product must only be installed or serviced by qualified personnel.
Please read this manual carefully before installation.
Keep this operation manual for future reference.
Original instructions
AU042FPERA
AU052FPERA
AU062FPERA
AU04IFPERA
AU05IFPERA
AU06IFPERA

Advertisement

loading

Summary of Contents for Haier AU042FPERA

  • Page 1 Installation Manual for Outdoor Unit AU042FPERA AU052FPERA AU062FPERA AU04IFPERA AU05IFPERA AU06IFPERA No. 0150521898 • This product must only be installed or serviced by qualified personnel. Please read this manual carefully before installation. Keep this operation manual for future reference. Original instructions...
  • Page 2: Table Of Contents

    User Manual Contents All the products are in conformity with the following Product Features ............1 European provision: -Low voltage Directive Safety ................1 -Electomagnetic Compatibility Transportation and Lifting ..........3 Installation instruction ............ 4 Electric wiring and the application ....... 13 Warning Installation and debugging...........
  • Page 3: Product Features

    Product Features • The outdoor uint adopts "simultaneous control" type, all indoors should be heating or cooli.ng simultaneously. • To protect compressor,before startup,the unit should be electrified for 12 hours.If the unit is not used for a long time, please cut off the power to save energy, or the unit will consume the power. This manual describes the installation and installation of outdoor units.
  • Page 4 Safety • The maintenance cover plate of the indoor or outdoor machine is forbidden when the main circuit power supply is not cut off. • The leakage of refrigerant can cause the air to be thin and difficult to breathe. In case of refrigerant leakage, close the main valve, extinguish any flame and contact the local distributor immediately.
  • Page 5: Transportation And Lifting

    Transportation and Lifting Lifting Over 60 degrees In front of the unit shipped from unpacking location as close rope as possible. 0.7~1.0 meters CAUTION • Do not place anything on the device. • Two ropes shall be used for lifting the outdoor unit. Hoisting method Hoisting to ensure that the level of outdoor machine, slowly Do not remove...
  • Page 6: Installation Instruction

    Installation instruction In installation, please check specially the below items: • If the connected units quantity and the total capacity is in the allowable range? • If the refrigerant pipe length is in the limited range? • If the pipe size is proper? And if the pipe is installed horizontally? •...
  • Page 7 Installation instruction Note: 1. In snowy area, install the unit under the bracket or the snow-proof cover against the accumulative snow on the unit. 2. Do not install the unit at the place where the flammable gas will leak. 3. Install the unit at the strong enough place. 4.
  • Page 8 Installation instruction (3) Multi-unit installation in front and back (unit: in.(mm)) The top and two side surfaces must be exposed to open space, and barriers on at least one side of the front and back shall be lower than the outdoor unit. •...
  • Page 9 • After punching the knock-out hole, the the min. thickness. application of repair-type paint on the 3. The branch pipe must be from Haier. surface around the edge sections is 4. When installing the stop valve, refer to the relative operation instruction.
  • Page 10 Installation instruction Pipe specification: 1. Pipe "a" diameter (between indoor and branch pipe) (depends on indoor pipe) Please refer to the indoor air conditioner manual. 2. Pipe "b" diameter (between branch pipes) Total indoor capacity after the branch pipe (x100W) Gas pipe (mm) Liquid pipe (mm) X<112 Ø15.88...
  • Page 11 Installation instruction Long pipe and high drop 1. Allowable pipe length and height difference Outdoor unit First branch piping Indoor unit Length of the longest piping L Length of the longest piping after the h≤10m first branch piping L Maximal length and drop height permissible of refrigerant piping Permissible value Piping part Total length of piping (actual length)
  • Page 12 Installation instruction Note: 1. When connecting the pipe and the outdoor, please pay attention to the outdoor pipe dimension. 2. When adjusting the diameter among pipes and among the units, please must execute at the branch pipe side. 3. When welding with hard solder, please must blow nitrogen. If not, a number of oxide will be produced and cause heavy damage.Besides,to prevent water and dust into the pipe, please make the brim as outer roll.
  • Page 13 Installation instruction • Weld the pipe at the same time charge the nitrogen. Or it will cause a number Seal the pipe end with of impurity (a film of oxidation) to clog the capillary and the expansion valve, adhesive tape or the stopper further cause the deadly failure.
  • Page 14 Installation instruction Because the unit is with refrigerant R410A, the below issues should be paid attention: • To prevent the different oil into the pipe, please use the special tool for R410A, especially for gauge manifold and charging hose. • To prevent the compressor oil into the refrigerant cycle, please use the anti-counter-flow adapter. (8) Check vale operation Open/close method: •...
  • Page 15: Electric Wiring And The Application

    Electric wiring and the application WARNING Inspect • Switch off the main power switch of the indoor • To ensure that the electrical equipment used on the installation and outdoor machine for more than 1 minutes site (main power switch, circuit breaker, wire, conduit and wiring before the wiring or regular inspection.
  • Page 16 Power circuit breaker (A) section breaker Section source Ground fault interruptor (mA) Screw response time (S) Model AU042FPERA 50A 30mA below 0.1S 1PH, AU052FPERA 220-230V~, 50A 30mA below 0.1S 50/60Hz AU062FPERA 50A 30mA below 0.1S AU04IFPERA 20A 30mA below 0.1S...
  • Page 17 Electric wiring and the application • When power cable exceeds the range, thichen it appropriately. • The appliance shall be installed in accordance with national wiring regulations. • All wiring must be performed by an authorized electrician. • Be sure to install an earth leakage circuit breaker in accordance with applicable legislation.Failure to do so many cause electrical shock.
  • Page 18 Electric wiring and the application Outdoor unit electrical wiring diagram Ground wire Power cord Communication line Fixing the power line and communication line with a wire clip on the partition board Power lines and communication lines need to be flame retardant and high temperature resistant wire wrap Cable sheath...
  • Page 19: Installation And Debugging

    Installation and debugging 1. Installation and debugging method of outdoor machine SW01 SW02 Seven segment digital tube display content Outdoor machine fault code The machine units are not locked and no fault, in turn cycle "in the machine number, machine capacity, power supply type".
  • Page 20 Installation and debugging SW01 SW02 Seven segment digital tube display content Forced heat alternating display "HHH" (according to Start 5 seconds to enter, all the internal mechanism of hot running, press Stop to exit for 5 seconds). Communication shows the program version (1 decimal), or "---" The machine type: (0:common indoor machine;...
  • Page 21 Installation and debugging 3. Outdoor unit PCB dipswitch setting, attention the different PCB version. In the following table, 1 is ON, 0 is OFF. BM1 introduction Begin to search indoor BM1_1 Indoor searching after startup Stop searching indoor and lock the quantity BM1_2 Secondary subcooling selected Yes (default) AC motor...
  • Page 22: Failure Code

    Failure code Inverter outdoor unit failure code Digital tube Indication indication on wired Failure code Failure description Remarks on master controller definition unit (hex) Defrosting temp. AD value is below 11(open circuit) or over 1012(short circuit) 20-0 sensor Te failure for 60seconds, in cooling mode, if the sensor is abnormal, Resumable the unit does not deal with it, besides, in defrosting and...
  • Page 23 Failure code Digital tube Indication indication on wired Failure code Failure description Remarks on master controller definition unit (hex) After compressor is running, compression ratio 8. for Once Compression ratio continuous 5 minutes stop and alarm.2 minutes and 50 39-1 39-1 confirmation, too high protection...
  • Page 24 Failure code Digital tube Indication indication on wired Failure code Failure description Remarks on master controller definition unit (hex) Valve plate module error(sending by Reserved Resumable valve plate) Once Valve plate dial No valve plate module dial but the valve plate module is confirmation, setting error detected.
  • Page 25 Failure code Digital tube Indication indication on wired Failure code definition Failure description Remarks on master controller unit (hex) Voltage too low of DC bus 3 times in an Voltage of power source is too low line of transducer hour, confirm failure;...
  • Page 26: Trial Operation And The Performance

    Trial operation and the performance Confirm the type of outdoor machine and the number of inside machine • After installation, please confirm that the outdoor computer board BM1_1 is in the 0 state, and then to the unit power, observe the digital display. If the number of the indoor machine and the outdoor machine type, the power supply voltage is correct, then the BM1_1 dial to 1 of the state, if it is not correct, please check the dial machine communication code and models, do not force the BM1_1 dial to 1 of the state, it may cause failure of the system.
  • Page 27 Trial operation and the performance Trial operation • Before trial operation: Before being electrified, measure the resistor between power terminal block (live wire and neutral wire) and the earthed point with a multimeter, and check if it is over 1MΩ. If not, the unit can not operate. To protect compressor, electrify the outdoor unit for at least 12 hours before the unit runs.If the crankcase heater is not electrified for 6 hours, the compressor will not work.