Replacing the fan

The fan in the unit has an expected lifespan of approximately 5 years.
Replace it when the Error Lamp is lit and the fan is stopped.
When this product is used in compliance with UL standards
or CE marking, do not replace the fan.
 Fan replacement does not comply with UL standards or CE
marking.
Do not insert your hand or metal objects into the fan
recess.
 Doing so may cause electric shock or short-circuit.
Do not put your fingers into the fan.
 The fan spins when connecting the AC input.
 Doing so may result in injury.
Before turn off the "Power", disconnect the AC Input Plugs
from a wall outlet (commercial power source).
BU150R
Caution (for replacing the fan)
4 Maintenance and Inspection
4-3 Replacing the fan