Mirage IVEH121A Owner's Manual page 47

Table of Contents

Advertisement

If refrigerant piping is already embedded in the
wall, do the following:
1. Hook the top of the indoor unit on the upper
hook of the mounting plate.
2. Use a bracket or wedge to prop up the unit,
giving you enough room to connect the refriger-
ant piping, signal cable, and drain hose. Refer to
Fig. 3.11 for an example.
UNIT IS ADJUSTABLE
Keep in mind that the hooks on the mounting plate are smaller than the holes on the back of the unit.
If you find that you don't have ample room to connect embedded pipes to the indoor unit, the unit can
be adjusted left or right by about 1.25-1.95in, depending on the model. (see Fig. 3.12).
Fig. 3.11
Fig. 3.12
3. Connect drain hose and refrigerant piping
(refer to Refrigerant Piping Connection section of
this manual for instructions).
4. Keep pipe connection point exposed to per-
form the leak test (refer to Electrical Checks and
Leak Checks section of this manual).
5. After the leak test, wrap the connection point
with insulation tape.
6. Remove the bracket or wedge that is propping
up the unit.
7. Using even pressure, push down on the bot-
tom half of the unit. Keep pushing down until the
unit snaps onto the hooks along the bottom of the
mounting plate.
47