Installing the drain pipe

Installing the drain pipe
Use a spirit level to make sure that product is horizontally leveled.
Choose one of the 2 drain holes on the bottom of the product and insert the provided drain plug, then connect the drain
pipe.
From the 2 drain holes, block the unused hole with the provided rubber plug.
Install the drain pipe at the rear side of the unit to get a sufficient space for repairs and service on the front side.
Do not install a trap on the pipe and install the drain pipe horizontally with a slope of 1/50 or more to prevent water from
flowing backwards.
For smooth drainage, install an air vent that is open to air.
Insulate the drain pipe and drain plug with insulation over 10 mm.
Install self-regulating heat cable on the drain pipe to prevent it from being frozen.
Install the safety equipment for a heating appliance.
Open to air
Drain plug
More than
1/50 slope
When concentrated drainage is installed
Install a concentrated drain pipes with an air vent that is open to air.
Drain plug
More than 1/50 slope
Checking the water leakage
Prepare about 2 liters of water and pour water into the drain pan of the DVM Hydro unit / Hydro unit HT as shown in the
illustration.
<DVM hydro unit>
Open to air
<DVM hydro unit HT>