Sequential Control Macro; Operation Diagram - ABB +N5600 Firmware Instructions

Single drive
Table of Contents

Advertisement

142 Application macros

Sequential control macro

The Sequential control macro is suited for speed control applications in which a
speed reference, multiple constant speeds, and two acceleration and deceleration
ramps can be used.
Only EXT1 is used in this macro.
The macro offers seven preset constant speeds which can be activated by digital
inputs DI4...DI6 (see parameter
reference can be given through analog input AI1. The reference is active only when
no constant speed is activated (digital inputs DI4...DI6 are all off). Operational
commands can also be given from the control panel.
The start/stop commands are given through digital input DI1; running direction is
determined by DI2.
Two acceleration/deceleration ramps are selectable through DI3. The acceleration
and deceleration times, as well as ramp shapes, are defined by parameters
23.12...23.19.

Operation diagram

The figure below shows an example of the use of the macro.
Speed
Speed 3
Speed 2
Speed 1
Start/Stop
Accel1/Decel1
Speed 1
Speed 2
Accel2/Decel2
Speed 3
22.21 Constant speed
Accel1
Accel1
function). An external speed
Stop along deceleration
ramp
Accel2
Decel2
Time