Default Control Connections For The Pid Control Macro - ABB +N5600 Firmware Instructions

Single drive
Table of Contents

Advertisement

138 Application macros

Default control connections for the PID control macro

P
I
Fault
XPOW External power input
1
+24VI
24 V DC, 2 A
2
GND
XAI
Reference voltage and analog inputs
1
+VREF
10 V DC, R
2
-VREF
-10 V DC, R
3
AGND
Ground
4
AI1+
Speed reference
0(2)...10 V, R
5
AI1-
6
AI2+
Process feedback*
0(4)...20 mA, R
7
AI2-
XAO
Analog outputs
1
AO1
Motor speed rpm
0...20 mA, R
2
AGND
3
AO2
Motor current
0...20 mA, R
4
AGND
XD2D Drive-to-drive link
1
B
Master/follower, drive-to-drive or embedded fieldbus
2
A
interface connection
3
BGND
XRO1, XRO2, XRO3 Relay outputs
1
NC
2
COM
3
NO
1
NC
2
COM
3
NO
1
NC
2
COM
3
NO
XD24
Digital interlock
1
DIIL
Digital interlock. By default, not in use.
2
+24VD
+24 V DC 200 mA
3
DICOM
Digital input ground
4
+24VD
+24 V DC 200 mA
5
DIOGND Digital input/output ground
XDIO
Digital input/outputs
1
DIO1
Output:
2
DIO2
Output:
XDI
Digital inputs
1
DI1
Stop (0) / Start (1) – Speed control
2
DI2
By default, not in use.
3
DI3
Speed control (0) / Process control (1)
4
DI4
Constant speed 1 (1 = On)
5
DI5
Run enable (1 = On)
6
DI6
Stop (0) / Start (1) – Process control
Safe torque off circuits must be closed for the drive to start. See
XSTO
Hardware manual of drive.
X12
Safety options connection
X13
Control panel connection
X205
Memory unit connection
*For sensor connection examples, see page 139.
1...10 kohm
L
1...10 kohm
L
> 200 kohm
in
= 100 ohm
in
< 500 ohm
L
< 500 ohm
L
Ready run
250 V AC / 30 V DC
2 A
Running
250 V AC / 30 V DC
2 A
Fault (-1)
250 V AC / 30 V DC
2 A
Ready run
Running

Hide quick links: