IC695ACC402 Quick Start Guide, GFK-2939. Secure the two retention flat-head
screws with a very small slotted screwdriver.
3. Set the pair of hook tabs at top rear of the CPU module into two adjacent notches
on the alignment rail of the RX3i rack backplane. This aligns the module with the
intended slots in the main rack and with the right-side connector of this pair.
4. Swing the module down until the rear connector on the CPU module engages the
mating backplane connector. Firmly engage the connectors.
5. Visually inspect the module to be sure it is properly seated.
6. Using a Phillip's head screwdriver, secure the two captive M3x5 machine screws
into the matching threaded holes in the backplate of the RX3i I/O rack. The two
screws are located at the bottom rear of the CPU module. Tighten.
7. Apply power to the rack.
Note: When the ACC402 Energy Pack is powered up, a period of time is required to
charge it up to its operating level. During this time, the Energy Pack will
indicate this condition via its LEDs (refer to PACSystems RX3i Energy Pack
IC695ACC402 Quick Start Guide, GFK-2939).
The CPE330 will begin its boot cycle once ACC402 is charged. This typically
takes 90 seconds or less. In the event the ACC402 is faulty or is not
communicating, CPE330 commences operation without the Energy Pack.

3.3. Redundancy Configuration

PROFICY Machine Edition 8.60 SIM 8 or later may be used to create native CPE330
redundant applications. To enable redundancy in a CPE330 project, select the CPE330
target in the PME Navigator and use the Property Inspector to change the
Enable Redundancy target property to True.
GFK-2941E
May 2016
12