Air-Cooled Scroll Chiller, Water-Cooled Scroll Chiller - LG ACP IV ACP Owner's Manual

Table of Contents

Advertisement

38
USING THE PROGRAM

Air-cooled scroll chiller, water-cooled scroll chiller

Air-cooled and water-cooled is separated according to the refrigerant (cooling in air: air, liquid-
cooled: water). Functions and menus are the same, but there is a difference in the range and set
temperature, etc.
The following menu controls the configuration and function of the air-cooled scroll chiller, water-
cooled scroll chiller.
Item
Operation
GoTo
Mode
Mode Target
Temp (℃)
Demand limit
[Apply] Button
[Detail. ▶] Button
y [ON] Button: Starts the operation of the device.
y [OFF] Button: Stops the operation of the device.
y [Schedule ▶] Button: Move to Schedule menu.
y [View Details ▶] button: Moves to detail information screen.
y [COOL] Button: Operates with Cooling Mode.
y [HEAT] Button: Operates with Heating Mode.
Click(Touch) [▲]/[▼] to set the mode set temperature.
y Air-cooled scroll chiller
- COOL: 5 ℃~15 ℃
- HEAT: 35 ℃~55 ℃
y water-cooled scroll chiller
- COOL: 5 ℃~15 ℃
- HEAT: 40 ℃~57 ℃
As measured at 1minute intervals the power consumption of the refrigerator,
the current power consumption does not exceed a target power consumption,
demand rate limit, function to lower the operation rate of the current.
Click(Touch) the [▲] / [▼] button to set a limit on the rate of demand.
y air-cooled scroll chiller: 0~120 (10 units)
y water-cooled scroll chiller: 0, 30~120 (10 units)
Apply control menu setting to the device.
Controls details.
Description

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

BacnetAc smartIv ac smart

Table of Contents