LG ACP IV ACP Owner's Manual page 116

Table of Contents

Advertisement

108
USING THE PROGRAM
Chiller
Item
Device Type
Unit Name
(20 Characters)
Address
Model
(20 Characters)
Capacity
Add at once
NOTES
Chiller is optional. It can be activated by installing additional CHILLER OPTION program.
y
Address of the products linked to the MODBUS communication system recommend a number
y
between 01~F7.
Select a device type.
y Water-cooled scroll/Air-cooled scroll/Turbo/Screw/ABS chiller
Enter the device name.
y Up to 20 characters.
Type the central control address of the device.
y A central control address value is a number between 00 and FF. You
cannot type the same value for similar devices.
Type the device model.
y Up to 20 characters.
Type the maximum capacity in thousand BTUs for devices.
y Up to 5 characters.
y The capacity of the actual device cannot exceed the input value.
It is used when you need to add several devices of the same type.
Select check box, input the desired number of devices, and the devices
are added at once, and the device name and address are automatically
increased. (During the Add all, if duplicate address value occurs, the
information notice message for the duplicate address is displayed.)
Description