LG ACP IV ACP Owner's Manual page 122

Table of Contents

Advertisement

114
USING THE PROGRAM
• AO
Item
Icon Type
Unit Name
(20 Characters)
Address
Use
Unit Symbol*
I/O Type
Min.*
Max.*
Range*
Correction*
Enable
Select a icon type
Enter the device name.
y Up to 20 characters.
It is automatically input according to Exp.I/O address, and it cannot be
changed.
Select device usage
y Number information: temperature, humidity, open, level, operation
ratio, concentration, pressure
Select unit symbol
y It is automatically selected according to the usage selection.
Dedicated VOL
Input minimum value
y You can input up to 5 digits
Input maximum value
y You can input up to 5 digits (Maximum two step AO output)
Select signal output required 0-10 or 2-10 VDC.
Input correction value
y You can input up to 5 digits
During Exp.I/O registration, 14 Points are available for registration, the
enable check box must be selected to enable use.
Description