Mitsubishi Electric CC-Link IE Basic Reference Manual page 46

Field network
Hide thumbs Also See for CC-Link IE:
Table of Contents

Advertisement

Displayed items
Item
Total Slave (Parameter)
IP Address
Error Code
[Error Details] button
Link Scan Time/Error Stations
Diagnostics Target Group
Station No.
Occpd Stns
Reserved Station
IP Address
Transmission Status
Disconnections
Time-out Count
The Latest Error
Error Details...
[Clear Latest Error Code] button
*1 The possible reasons include that the slave station set in parameter has not started up, a cable between the master station and the
slave station is disconnected, or the setting of an IP address or a subnet mask of the master/slave station is incorrect.
*2 Take actions and eliminate the error cause first. Then, clear the error code.
*3 When the count exceeds 65535, counting is continued from 1 again.
*4 For details on an error of the slave station, GX Works3 of "1.040S" or later supports. (Page 58 Added and Enhanced Functions)
For the error codes, refer to the manuals of each series.
 MELSEC iQ-R CPU Module User's Manual (Application)
 MELSEC iQ-F FX5 User's Manual (Application)
 QCPU User's Manual (Hardware Design, Maintenance and Inspection)
 MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and Inspection)
The following indicates that the disconnection has occurred due to no cyclic transmission caused by the cable
disconnection of the master station side. In this case, the previous cyclic transmission time (just before the
disconnection) is displayed on the link scan time.
• "CFE8" is displayed as the latest error for all slave stations. (No response received from a slave station)
• "No Error" is displayed on the error code of the master station.
9 TROUBLESHOOTING
44
9.1 CC-Link IE Field Network Basic Diagnostics
Description
The total number of slave stations set in parameter is displayed.
The IP address of the master station is displayed. The display can be switched between decimals and hexadecimals in
"Change IP Address Display".
The error code of the master station is displayed.
The description of the error and the actions to be taken are displayed.
Link scan time (present, maximum, minimum) and number of error stations/unfixed stations of each group is displayed.
Error stations (Error Stns) and unfixed stations (Unfixed Stns) refers the following state.
• Error Stns: Stations where an error has been occurred
• Unfixed Stns: Stations (not including reserved stations) where the transmission status has not been fixed
Select a group to display its diagnostic information list.
The station number of the slave station is displayed.
The number of occupied stations set in parameter is displayed.
The reserved station status set in parameter is displayed.
The IP address set in parameter is displayed.
"-" is displayed when the station is a reserved station and an IP address has not been set.
The transmission status of the slave station is displayed.
• Unfixed: Communications with the master station not established
• Transmitting: Cyclic transmission being performed
• Disconnecting: Disconnected from the master station
The accumulated number of disconnection detection is displayed.
• 0: No disconnections
• 1 to 65535: Number of disconnection detection (accumulated number)
The accumulated number of timeouts is displayed.
• 0: No timeouts
• 1 to 65535: Number of timeouts (accumulated number)
*4
The latest error code
is displayed an error on the transmission status between the master station and slave stations
detected by the master station or an error which has occurred in a slave station. When the slave station is
disconnected, an error occurs. After that, even when the disconnected slave station returns to the system, the error is
held. When another error occurs, the latest error will be updated (overwritten).
When both errors occur, the priority of errors to be displayed is as follows.
(1) An error which has occurred in a slave station
(2) An error on the transmission status between the master station and slave stations detected by the master station
For an error of the slave station, check 'Diagnostic information 2' (Un\G1068 to Un\G1077). ( Page 48 Acquiring
diagnostic information of slave stations)
The description of the error and the actions to be taken are displayed.
*2
The error code is cleared.
The button can be clicked only during monitoring.
*1
*3
*3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents