III.

WIRING.

Warning! Read Safety Warning on page 1
!
before attempting to use this control.
Warning! To avoid erratic operation do not bundle AC
Line and motor wires with potentiometer, voltage fol-
lowing, enable, inhibit or other signal wiring.
shielded cables on all signal wiring over 12" (30 cm) –
Earth ground the shield on the drive side only.
A.
AC Power – The KBSI-240D is powered with either 115
or 230V AC, 50/60 Hz by arranging the jumpers
between terminals "1" to "4" properly. See figures 2A
and 2B. Be sure unit is wired in accordance with the
National Electric Code and other codes that may apply.
It is recommended that a 1 amp fuse be installed in
series with the AC line.
B.
Input Terminals – A voltage or current signal from a
microprocessor, tachometer, transducer, etc. is to be con-
nected to terminals "5" through "8." The selection of the
proper terminal is based on the maximum level of the input signal. See figures 3 and 4.
FIGURE 2A – 115V CONNECTION
1
2
Jumper
Use
115V AC
FIGURE 2B – 230V CONNECTION
1
2
230V AC
3
4
Jumper
1A
FUSE
3
4
Jumper
1A