Setting Guidelines; Rated System Frequency Primval; Identification; Application - ABB REQ650 Applications Manual

Breaker protection, relion 650 series
Hide thumbs Also See for REQ650:
Table of Contents

Advertisement

Section 16
Basic IED functions
16.4.2
16.5
16.5.1
16.5.2
16.5.3
16.6
16.6.1
292

Setting guidelines

The setting ActiveSetGrp, is used to select which parameter group to be active. The
active group can also be selected with configured input to the function block
SETGRPS.
The length of the pulse, sent out by the output signal SETCHGD when an active
group has changed, is set with the parameter t.
The parameter MAXSETGR defines the maximum number of setting groups in use
to switch between. Only the selected number of setting groups will be available in
the Parameter Setting tool (PST) for activation with the ActiveGroup function
block.

Rated system frequency PRIMVAL

Identification

Function description
Primary system values

Application

The rated system frequency and phase rotation direction are set under Main menu/
Configuration/ Power system/ Primary Values in the local HMI and PCM600
parameter setting tree.
Setting guidelines
Set the system rated frequency. Refer to section
SMAI"
for description on frequency tracking.

Summation block 3 phase 3PHSUM

Application
The analog summation block 3PHSUM function block is used in order to get the
sum of two sets of 3 phase analog signals (of the same type) for those IED
functions that might need it.
IEC 61850
IEC 60617
identification
identification
PRIMVAL
-
"Signal matrix for analog inputs
Breaker protection REQ650 2.2 IEC
1MRK 505 383-UEN A
M15259-3 v4
IP15064-1 v2
GUID-B8B3535D-227B-4151-9E98-BEB85F4D54DE v1
ANSI/IEEE C37.2
device number
-
M15288-3 v6
M15292-3 v2
SEMOD55968-1 v2
SEMOD56004-4 v3
Application manual