SPECIFICATIONS
Load Voltage
Max Load
Min Load
Capacity
Battery Type
Battery Life
Charge Voltage
Over-discharge
protection
VAC +/- 10%
Input Current
Enclosure Type
Operating
Temp
3. VENTING: The enclosure is vented thru the wire feedthrus and vari-
ous hole plugs in the bottom of the enclosure. Don't make these airtight
with silicon
4. BATTERY MAINTENANCE: The batteries used in the UPSPro sys-
tems don't require any maintenance. They should last up to 5 years in
normal use. Note: Never store batteries for any length of time in a
discharged state or it will kill the battery.
5. BATTERY OVERDISCHARGE: We highly recommend hooking all
equipment loads to the controller voltage output. This output will discon-
nect the load if the battery voltage drops below the set voltage and this
will protect the battery from over-discharge. If batteries get completely
discharged because the equipment was connected directly to the bat-
tery, you will reduce the battery life. Discharged batteries will freeze at
very low temperatures. If the batteries get discharged less than 10V you
will need to recondition them by charging them with a good 10A auto-
motive battery charger. Don't charge for more than 24hrs else you
UPS-ST12
12V +/-0.5
10A (120W)
1A
1 battery 51Ah
600VA
2 battery 102Ah
1200VA
4 battery 204Ah
2400VA
Valve Regulated Sealed Lead Acid / GEL
WET Equalize =
14.6V, Float =
13.2V
GEL Equalize =
14.2V, Float =
13.5V
10.7V Load Off
12.6V Load On
Selector Switch 120VAC / 240VAC , 50/60Hz
3.5A @ 115VAC / 1.8A @ 240VAC
6
Subject to change without notice
UPS-ST24
24V +/- 0.5
5A (120W)
1A
2 battery 51Ah
1200VA
4 battery 102Ah
2400VA
5 Years
WET Equalize =
28.8V, Float =
26.4V
GEL Equalize =
28.4V, Float =
27V
21.5V Load Off
25.2V Load On
Powder Coat Steel
-30°C to +60°C
UPS-ST48
48V +/- 0.5
2.5A (120W)
1A
4 battery 51Ah
2400VA
WET Equalize =
58V, Float = 53V
GEL Equalize =
56.8V, Float =
54V
40V Load Off
51V Load On