Connecting Power - Mitsubishi Electric MelcoREMOTE Installation And Operation Manual

Table of Contents

Advertisement

7. Connecting power

A double pole (Live and Neutral) 5A switch or circuit breaker must be provided in line with the supply to the
MelcoREMOTE power supply and be in close proximity to it. It must be clearly marked as the disconnecting device for
the MelcoREMOTE.
Ensure the mains cable supplying the power to the MelcoREMOTE power supply is suitably rated for the intended
environment and current draw of the MelcoREMOTE.
Warning:
Electrical work should be done by qualified electrical engineers / electrician in accordance with "Engineering
Standards for Electrical Installation" and supplied installation manuals. Dedicated circuits should also be
used. If the power circuit lacks capacity or has an installation failure, it may cause a risk of electric shock or
fire.
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too
large capacity may cause a risk of malfunction or fire.
Be sure to take power from the special branch circuit
Install the unit to prevent any of the control circuit cables coming into direct contact with power
cables
Ensure that there is no slack on all wire connections
Never connect the power cable to leads for the transmission cables. This will damage the
transmission cables
Page 15 of 52

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melcoremote2g

Table of Contents