9.3. Configuration

The default IP address for all centralised controllers is 192.168.1.1 and subnet mask 255.255.255.0.
The default IP address for MelcoREMOTE is 192.168.1.2 and subnet mask 255.255.255.0.
When connecting Ethernet devices together each one needs to have a unique IP address.

9.3.1. PIN Codes

The following PIN codes must be entered to enable communication between the central controller and MelcoREMOTE.
The applicable centralised controller PIN code must be entered to enable communication with
MelcoREMOTE.
9.3.2. AE-200 / EW-50
The AE-200 and EW-50 controller has a setting called 'Old Model Compatibility Mode' which needs to be set to ON for
correct operation with MelcoREMOTE. This setting can be accessed through the 'Initial Setting' screen under the
'Advanced' tab or embedded webpage for the AE-200, for the EW-50 it must be changed through the embedded
webpage.
All AE-200 and EW-50 controllers must have their 'Old Model Compatibility Mode' setting set to ON for
correct operation with the MelcoREMOTE.
Page 21 of 52
Controller Type
G-50
GB-50
AG-150
AE-200 / EW-50
PIN Code required
G50-WebMonitor
GB50-Basic
AG150-Basic
(no PIN required)