2. DEVICE IDENTIFICATION

Manufacturer Name:
Manufacture ID Code:
HART Protocol Revision
Number of Device Variables
Physical Layers Supported
Physical Device Category
The FS24X HART® module is identified by a serial number that begins with "24X-". This
serial number will be visible on the module circuit card, along with a bar code containing the
same information.
The FS24X is designed to detect fire in a hazardous area. This device should be mounted so
as to avoid areas that contain non-fire radiant energy sources (such as radiant heaters, high
intensity lamps, etc.) in close proximity to the detector's field of view. FS24X detectors
should be mounted so that they look downward with minimum twenty degree (20°) angle.
Avoid mounting the detectors in areas where temperatures are outside the specified operating
temperature range
INSTALLATION) for mounting instructions.

3. PRODUCT OVERVIEW

The FS24X is a Multi-Spectrum Flame Detector. A HART® communication module is
required for HART® communication.

4. PRODUCT INTERFACES

4.1 Process Interface

4.1.1 Sensor Input Channels

Fire Sentry multi-spectrum and multi-spectral infrared Flame Detectors are sophisticated,
state of the art, electro-optical digital radiant energy transducers that sense Wideband Infrared
radiant energy emitted by fire's combustion processes that include molecular emissions and
hot particulate blackbody emissions
WideBand 4.3 IR "Triple IR" region from approximately 3 to 5 microns.
FS24X Detectors also utilize additional spectral regions, the Visible Band and Near Band
Infrared wavelengths, to aid in discrimination against non-fire false alarm sources.

4.2 Host interface

4.2.1 Analog Output 1: Loop Current

Loop current is the only output from this transmitter, representing the presence of flame in
the range of the instrument, as well as fault status. This output corresponds to the Primary
Variable. Refer to the section 4.3.3 for connection details.
Revision 1.2, Release Date: 15 February 2013
Honeywell
Analytics
210
(D2 Hex)
7.0
None
FSK
Sensor and Transmitter
(-40°C to +85°C). Refer to the FS24X manual (SECTION 2:
Additionally, the FS24X Detectors sense the specific
.
Model Name(s):
Device Type Code:
Device Revision:
Fire Sentry Corporation
FS24X
130
(82 Hex)
1
Page 5 of 16