Lenel AES Firmware is embedded (installed) in the LNL-3300-M5 (firmware version 1.2xx) for suitability
as "Encrypted Line Security Equipment." (Refer to the release notes for the supported firmware versions.
The release notes are located on the root directory of the OnGuard installation disc.)
Note:
If the central supervisory station receives a "Communication Loss" message, a compromise
attempt on the communication line may have occurred.
Network addressing of devices shall not make use of public domain name servers.
Panic hardware must be UL 305 Listed.
5.1

Power

The standby power system for the HVAC system may be supplied by an engine-driven generator alone. Use
of a standby battery is not required.
All external interconnecting power sources must be UL Listed access control/proprietary burglar power
limited power supplies. AC supply lines shall not be routed in the same conduit or harness as low voltage
lines.
5.2

UL Certified Power Supplies

For the UL certification, the power supply that must be used is the LNL-AL400ULX or LNL-AL600ULX-
4CB6 with additional hardware mounted in LNL-CTX or LNL-CTX-6 enclosures. Other power supplies
will be certified for use at a future date.
For the ULC Certification, hardware must be mounted in an LNL-CTX or LNL-CTX-6 enclosure. All power
supplies must be UL, ULC, or cUL Listed for security applications, and power-limited.
Output
M3000
12 VDC/
12 AH
Battery
M-5 UTC
12 VDC/
F&S
7 or 12 AH
PS/C-6 or
Battery
AL400UL
5.3

Typical Combinations for UL Installations

The following combinations must be used in a UL type installation with OnGuard 7.x or later, which are
approved for use. For UL certification, a UL Listed power supply and one of the following enclosures must
be used:
4 hr. of Stand-by &
24 hr. of Stand-by & 5
5 minutes of Alarm
Minutes of Alarm
Stand-by = 4.0 amps
Stand-by = 1.0 amp
Alarm = 4.0 amps
Alarm = 4.0 amps
Stand-by = 6.0 amps
Stand-by = 1.0 amp
Alarm = 6.0 amps
Alarm = 6.0 amps
M Series Installation Guide
60 hr. of Stand-by &
5 Minutes of Alarm
Stand-by = 300 mA
Alarm = 4.0 amps
Stand-by = 300 mA
Alarm = 6.0 amps
revision 7 —
29