Power And Communications - Lenel LNL-1300-U Quick Reference

Single door controller module
Table of Contents

Advertisement

Overview of Elevator Control
Maximum:
4000 feet
(1219.2 meters)
5 conductors
Single
Single
Reader
Reader
Interface
Interface
Module
Elevator
Reader
(inside cab)
External (Cabinet) Tamper
An external cabinet tamper is configured by connecting a tamper device
across pins 3 & 4 of J18 on the SDC. If not used, a jumper must be installed
across pins 3 & 4 of J18.
Note:
Power fail is not supported on the SDC; therefore no jumper is
required. This is labeled in the diagram as "NOT USED."
External tamper wiring
Note:
Input status LEDs will be off when the tamper device is in closed
position or the jumper is installed.
Access
Control
System
Intelligent System Controller
Output
Control
Module
Single Reader Interface
Up to 128 Outputs -
eight Output Control
Modules
Elevator Control Room

Power and Communications

For its power input, the SDC requires a 12 to 24 VDC ± 10% power source
for it input power.
Wire the power input with 18 AWG (minimum) twisted pair cable.
Power Source
DC power source
Input Control
Module
Up to 128 Inputs -
eight Input Control
Modules
Notes:
Be sure to observe polarity.
Do not use an AC transformer to directly power the Single Door
SDC Interface Module.
7
Requirements
Current
Isolated, non-switching,
700mA for 12VDC
regulated DC power
350mA for 24VDC
Power source wiring
460989001B