Lenel LNL-3300-M5 Installation Manual page 120

Intelligent system controller m series
Table of Contents

Advertisement

LNL-1320-S2RP Dual Door Control Module
36.2.1
Supervised Inputs wired to the LNL-1320-S2RP
Supervised inputs for the door position monitor and REX switches are wired to TB1 for the first reader, and
TB3 for the second reader. Two sets of End-Of-Line (EOL) resistor pairs are supported by the S2RP board.
Either two 1K ohm resistors, or a 6.8K and 18K ohm resistor set must be installed as shown in the following
figures. Install the EOL resistors as close to the switch as possible to maximize supervision's effectiveness.
In addition to detecting contact open or contact closed, the LNL-1320-S2RP also monitors for the following
abnormal circuit conditions: open circuit, shorted circuit, grounding of either side of the circuit, or the
introduction of a foreign voltage.
Note:
Grounded and foreign voltage states are not required by UL 294 and therefore not verified by
UL.
3
Supervised Input Wiring with 1K/1K EOL Callouts
Callout
Description
1
TB1 or TB3 on LNL-1320-S2RP
2
Normally Open contact for REX switch
120 —
revision 7
Supervised Input Wiring with 1K/1K EOL
1K,1%
2
1K,1%
1K,1%
1K,1%
1
VO
GND
DISP
LED
REX+
WD0
WD1
DC+
DC-
REX-