Troubleshooting; Error Code List - Sharp AY-X36RU Service Manual

Split type air conditioners
Hide thumbs Also See for AY-X36RU:
Table of Contents

Advertisement

AY-X36RU
AE-X36RU
Display Method of Indoor Unit
Indicator Display (during blink-
Malfunction
Dual 8
NO.
Name
Code
Operation
Display
Indicator
High pressure
OFF 3s
1
protection of
E1
and blink
system
once
OFF 3S
Antifreezing
2
E2
and blink
protection
twice
In defect of
3
F0
refrigerant
High discharge
OFF 3S
temperature
4
E4
and blink
protection of
4 times
compressor
OFF 3S
Over current
5
E5
and blink
protection
5 times
Communica-
OFF 3S
6
tion Malfunc-
E6
and blink
tion
6 times
High tempera-
OFF 3S
7
ture resistant
E8
and blink
protection
8 times
EEPROM mal-
8
EE
function
Limit/decrease
frequency
OFF 3S
9
due to high
EU
and blink
temperature of
6 times
module
Malfunction
OFF 3S
10
protection of
C5
and blink
jumper cap
15 times
OFF 3S
Gathering
11
Fo
and blink
refrigerant
1 times
Indoor ambient
temperature
12
F1
sensor is open/
short circuited
Indoor evapo-
rator tempera-
13
ture sensor
F2
is open/short
circuited

TROUBLESHOOTING

[1] Error Code List

Display Method of Outdoor Unit
Indicator has 3 kinds of display
status and during blinking, ON
ing, ON 0.5s and OFF 0.5s)
Cool
Heating
Yellow
Indicator
Indicator
Indicator
OFF 1S
and blink
3 times
OFF 1S
and blink
7 times
OFF 1S
and blink
5 times
Always
ON
OFF 1S
and blink
6 times
OFF 3S
OFF 1S
and blink
and blink
11 times
15 times
OFF 3S
and blink
6 times
OFF 3S
OFF 1S
and blink
and blink
1 times
17 times
OFF 3S
and blink
once
OFF 3S
and blink
twice
0.5s and OFF 0.5s
Red
Green
Indicator
Indicator
During cooling and drying opera-
tion, except indoor fan operates, all
loads stop operation. During heat-
ing operation, the complete unit
stops.
During cooling and drying opera-
tion, compressor and outdoor fan
stop while indoor fan operates.
OFF 1S
The Dual 8 Code Display will show
and blink
F0 and the complete unit stops.
9 times
During cooling and drying opera-
tion, compressor and outdoor fan
stop while indoor fan operates.
During heating operation, all loads
stop.
During cooling and drying opera-
tion, compressor and outdoor fan
stop while indoor fan operates.
During heating operation, all loads
stop.
During cooling operation, compres-
sor stops while indoor fan motor
operates. During heating operation,
the complete unit stops.
During cooling operation: compres-
sor will stop while indoor fan will
operate.
During heating operation, the com-
plete unit stops.
During cooling and drying opera-
tion, compressor will stop while
indoor fan will operate; During
heating operation, the complete
unit will stop
All loads operate normally, while
operation frequency for compres-
sor is decreased
Wireless remote receiver and but-
ton are effective, but can not dis-
pose the related command
When the outdoor unit receive sig-
nal of Gathering refrigerant
,the system will be forced to run
under cooling mode for gathering
refrigerant
During cooling and drying opera-
tion, indoor unit operates while
other loads will stop; during heating
operation,
the complete unit will stop opera-
tion.
AC stops operation once reaches
the setting temperature. Cooling,
drying: internal fan motor stops
operation while other loads stop
operation; heating: AC stop opera-
tion
10
A/C status
Possible Causes
Possible reasons:
1. Refrigerant was superabundant;
2. Poor heat exchange (including
fifth blockage of heat exchanger
and bad radiating environment );
Ambient temperature is too high.
1. Poor air-return in indoor unit;
2. Fan speed is abnormal;
3. Evaporator is dirty.
1. In defect of refrigerant;
2. Indoor evaporator temperature
sensor works abnormally;
3. The unit has been plugged up
somewhere.
Please refer to the malfunction
analysis (discharge protection, over-
load).
1. Supply voltage is unstable;
2. Supply voltage is too low and
load is too high;
3. Evaporator is dirty.
Refer to the corresponding malfunc-
tion analysis.
Refer to the malfunction analysis
(overload, high temperature resis-
tant).
Replace outdoor control panel AP1
Discharging after the complete unit
is de-energized for 20mins, check
whether the thermal grease on IPM
Module of outdoor control panel AP1
is sufficient and ahether the radiator
is inserted tightly. If its no use, please
replace control panel AP1.
1. No jumper cap insert on main
board.
2. Incorrect insert of jumper cap.
3. Jumper cap damaged.
4. Abnormal detecting circuit of
main board.
Nominal cooling mode
1. Loosening or bad contact of
indoor ambient temp. sensor and
main board terminal.
2. Components in main board fell
down leads short circuit.
3. Indoor ambient temp. sensor
damaged.(check with sensor
resistance value chart)
4. Main board damaged.
1. Loosening or bad contact of
Indoor evaporator temp. sensor
and main board terminal.
2. Components on the main board
fall down leads short circuit.
3. Indoor evaporator temp. sensor
damaged.(Check temp. sensor
value chart for testing)
4. Main board damaged.