Bosch ISN-SM-30 Application Manual page 41

Isn-sm-xx series seismic detectors and accessories
Table of Contents

Advertisement

reduction in the transferred signals to adjoining surfaces such as coverage from a wall-mounted
detector extending to the adjoining wall, ceiling or floor, is not depicted.
As construction methods of vaults may vary, the transfer of detection radius from one
surface to an adjacent surface should not form part of any calculation.
Figure 6-17: Example 2 - detector location and detection radius
Using a scale drawing of the room to be protected and adding the detection radius is a
good method of verifying a system design.
Surface &
Reference
Left hand wall
(C)
Ceiling (B)
Right hand wall
(E)
Bosch Security Systems
Detector-Reference Detector Setting
ISN-SM-90 - 1
ISN-SM-90 -2
ISN-SM-90 - 3
ISN-SM-90 - 4
ISN-SM-90 - 5
ISN-SM-90 - 6
Seismic Detectors Application Guide
Accessory for
Mounting
5m concrete
GMXW0
5m concrete
GMXW0
5m concrete
GMXP0
5m concrete
GMXP0
5m concrete
GMXW0
5m concrete
GMXW0
Design
6
Accessory for
Testing
GMXS5
GMXS1
GMXS1
GMXS5
41
I-200153-1
04.2016

Advertisement

Table of Contents
loading

This manual is also suitable for:

Isn-sm-80Isn-sm-50Isn-sm-90

Table of Contents