Replacement intelligent equipment gateway
Table of Contents

Advertisement

11. Click 'Save changes' button
a. IMPORTANT: Allow the page to refresh
b. Confirm that there is number in parentheses next
to "Review Changes". If so, proceed to step 12; if
not, repeat steps 8-11.
12. Remove 'wwan' interface
13. Remove 'wlan0' interface
14. Click the 'Save Changes' button
a. IMPORTANT: Allow the page to refresh
b. Confirm that there is number in parentheses next
to "Review Changes". If so, proceed to step 15; if
not, repeat steps 8-14.
15. Click the 'Apply Changes' button in the lower right-hand
corner of the screen. The page will automatically refresh
when complete (this can take as much as two minutes).
Figure 17: M2M Gateway Home Page
IM 1229-1 • INTELLIGENT EQUIPMENT
16. Confirm that 'ICMP host' of "wan" interface is still set to
"disable"
a. If so, go to step 17.
b. If not, set to "disable"
c. Click 'Save changes' button
i. IMPORTANT: Allow the page to refresh
ii. Confirm that there is number in parentheses
next to "Review Changes". If so, proceed to
step 17; if not, repeat steps 8-16.
d. Click the 'Apply Changes' button in the lower
right-hand corner of the screen. The page will
automatically refresh when complete (this can take
as much as two minutes).
17. Click the 'System' tab, then click the Reboot button.
18. Reconnect the Ethernet cable between the M2M
Gateway and the MicroTech III controller. Procedure
complete.
NOTE: Be certain that the IT staff has allowed incoming and
outgoing internet traffic on TCP ports 80, 443, 3197,
3199, 5222, 5223 and 8080.