EMS 5000 FirePoint Installation Manual page 4

Combined sounder
Hide thumbs Also See for 5000 FirePoint:

Advertisement

Con guration Switch Settings
The device is dispatched with con guration switches set as per Figure 6.
Switch 1: Tamper = disabled
Switch 2: Self sound = disabled
Switches 3/4: Volume = high
Tamper Disablement Feature
The device has a tilt operated tamper switch for removal detection. This feature can be enabled or
disabled using Switch 1.
Putting switch 1 to the ON position will disable the devices's tamper monitoring.
Self Sound Feature
The device has the ability to sound immediately upon entering an alarm condition, when the re panel
is used in visual delay mode. It is therefore possible for an individual area to be alerted without
evacuating the whole building.
To enable the self-sounding option, switch 2 must be in the ON position.
Sounder Volume
The device's sounder volume can be adjusted using the switches 3 and 4. The switch settings for the
volume are shown in gure 7.
Switch
3 & 4 On
settings
High
Medium
3 Off 4 On
Low
3 & 4 Off
MK235 Iss 4 20/12/2016 AJM
Figure 6
Figure 7