Advertisement

Setting Sensitivity

The device is able to detect either smoke or heat by simply changing the sensor's switch con guration.
This allows easy interchanging between heat and smoke modes without having to purchase a new
sensor. The sensitivity switch location is shown in Figure 3.
Figures 4 & 5 illustrate the dip switch settings to accomplish the required function from the sensor.
Smoke Sensitivity Settings
Sw
Sw
Sw
1
2
3
Off
Off
Off
Off
On
Off
On
Off
Off
On
On
Off
Heat Sensitivity Settings
Sw
Sw
Sw
1
2
3
Off
Off
Off
Off
On
Off
On
Off
Off
On
On
Off
X – Not Used
ROR – Rate of Rise
AVF - Accelerated Alarm Veri cation, to prevent false alarms due to transient smoke.
Please Note
The nal commissioning, detection sensitivity settings and hand over of the re system to the end user
is the responsibility of the re installation contractor.
L744-4
OFF
ON
L946-5
Placed on the market by
UTC Fire & Security.
Part no. 68701. See
Installation Sheet 1631.
ZR432-2 Radio Multisensor (Optical/Heat) Detector
FCZ-174-001
EN54-7
EN54-5 Class A 1
Made in South Africa
0359-CPD-0112
Sw
Sw
Sw
4
5
6
On
Off
X
On
Off
X
On
Off
X
On
Off
X
Sw
Sw
Sw
4
5
6
Off
On
X
Off
On
X
Off
On
X
Off
On
X
OFF
Placed on the market by
UTC Fire & Security.
Part no. 68701. See
Installation Sheet 1631.
ZR432-2 Radio Multisensor (Optical/Heat) Detector
FCZ-174-001
Sw
Mode of Operation
EN54-7
7
EN54-5 Class A 1
On
High Sensitivity
Made in South Africa
On
Normal Sensitivity
On
Low Sensitivity
On
Low Sensitivity + AVF
Sw
Mode of Operation
7
On
58°C ROR
On
58°C fixed
On
75°C fixed
On
82°C fixed
L744-4
ON
L946-5
Smoke Sensitivity %
Per M
1.6
0359-CPD-0112
2.3
3.0
3.0 + AVF
MK235 Iss 4 20/12/2016 AJM
Figure 3
Figure 4
Figure 5