Siemens SIMATIC ET 200SP Manual page 49

Interface, im 155-6 pn hs
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Open IE communication
TCP/IP
SNMP
LLDP
Isochronous mode
Isochronous mode (application synchronized up to
terminal)
Constant bus cycle time
Shortest clock pulse
Longest clock pulse
Bus cycle time (TDP), min.
Jitter, max.
Interrupts/diagnostics/status information
Status display
Interrupts
Diagnostic functions
Diagnostic indicator LED
RUN LED
ERROR LED
MAINT LED
Monitoring of the supply voltage (PWR LED)
Connection display LINK TX/RX
Electrical isolation
Between backplane bus and electronics
between PROFINET and all other circuits
Standards, approvals, certificates
Network loading class
Security level
Ambient conditions
Ambient temperature during operation
Horizontal installation, min.
Horizontal installation, max.
Vertical installation, min.
Vertical installation, max.
Dimensions
Width
Height
Depth
Weights
Weight, approx.
IM 155-6 PN HS interface module (6ES7155-6AU00-0DN0)
Manual, 09/2016, A5E34928647-AA
Technical specifications
6ES7155-6AU00-0DN0
Yes
Yes
Yes
Yes
Yes
125 µs
4 ms
125 µs
0.25 µs
Yes
Yes
Yes
Yes; green LED
Yes; red LED
Yes; yellow LED
Yes; green PWR LED
Yes; 2x green Link LED on BusAdapter
No
Yes
3
According to Security Level 1 Test Cases V1.1.1
0 °C
60 ℃
0 °C
50 ℃
50 mm
117 mm
74 mm
147 g; without BusAdapter
49