5.3.2

Channel diagnostics

Function
Channel-related diagnostics provides information about channel faults in modules.
Channel faults are mapped as channel diagnostics data in IO diagnostics data records.
The data record is read using the instruction "RDREC".
Structure of the diagnostics data records
The data records supported by the ET 200SP distributed I/O system are based on the
standard PROFINET IO - Application Layer Service Definition V2.3.
You can download the standard PROFIBUS user organization (http://www.profibus.com)
from the homepage of the PROFIBUS User Organization.
Codes of the extended channel diagnostics
With the IM 155-6 PN HS interface module, the following extended channel diagnostics are
reported:
Slot number
ChannelError-
Type (CET)
Module slot
0x0602
Slot 0
0x0602
0x0602
0x0602
0x0602
Server module slot 0x0610
IM 155-6 PN HS interface module (6ES7155-6AU00-0DN0)
Manual, 09/2016, A5E34928647-AA
ExtendedChannel-
Associated value
ErrorType (ECET)
AddValue
0x0691
Slot
0x0693
0x00
0x0698
0x00
0x0699
Slot
0x069C
0x00
0x06B0
0x00
Interrupts, diagnostics, error, and system messages
Diagnostics
Station stop - module parameter "Poten-
tial group" faulty or incorrect BaseUnit in
actual slot (AddValue)
Diagnostics with missing server module
Diagnostics backplane bus too long
Diagnostics with incorrect bus configura-
tion
Diagnostics with incorrectly plugged
BusAdapter
Group diagnostics: Missing supply volt-
age L+ for the potential groups
Note: The slot in which the light-colored
BaseUnit of the respective load module is
located is coded in the "ChannelNumber"
element.