RN/ER/MT LEDs on the interface module
Table 5- 1
Status and error displays of RN/ER/MT LEDs
LEDs
RN
ER
(RUN)
(ERROR)
Off
Off
On
On
Not relevant Not rele-
Flashes
Not relevant Not rele-
On
Not rele-
vant
Flashes
Not rele-
Not relevant
vant
Flashes
Flashes
Flashes
Flashes
Not rele-
vant
Flashes
* PWR LED on (on the interface module): Check the backplane bus for a short circuit.
IM 155-6 PN HS interface module (6ES7155-6AU00-0DN0)
Manual, 09/2016, A5E34928647-AA
MT
(MAINT)
Missing or insufficient supply voltage on
interface module.
Off
Test of LEDs during startup: The three
LEDs light up simultaneously for ap-
On
proximately 0.25 s.
Interface module is deactivated.
vant
Interface module is not configured.
ET 200SP starts up.
ET 200SP is being assigned parame-
ters.
ET 200SP is currently exchanging data
vant
with the IO controller.
Not rele-
Group errors and group error channels.
vant
The configured structure does not cor-
respond to the actual structure of the
ET 200SP .
Invalid configuration states.
Parameter error in the I/O module.
Maintenance
On
Not rele-
Invalid BusAdapter
vant
The "Node flash test" is run (the LEDs
LK1 and LK2 of the PROFINET inter-
Flashes
face also flash).
Hardware or firmware defective (the
LEDs LK1 and LK2 of the PROFINET
interface do not flash).
Configuration error on backplane bus
Flashes
Interrupts, diagnostics, error, and system messages
Meaning
5.1 Status and error displays
Remedy
Check the supply voltage or turn it on at the
interface module.*
---
Activate the interface module with the con-
figuration software or the user program.
Configure the interface module with the
configuration software.
---
---
Evaluate the diagnostics data and remedy
the error.
Check the structure of the ET 200SP to see
whether a module is missing or defective,
or whether a non-configured module is
plugged.
See section Invalid configuration states of
the ET 200SP on PROFINET IO (Page 44)
Evaluate the display of the module status in
STEP 7 and eliminate the error in the re-
spective I/O module.
See section Maintenance events (Page 42)
Check the BusAdapter.
---
Run a firmware update. If the error persists,
contact Siemens Industry Online Support.
Replace the interface module.
Insert the server module as bus termination
or check the number of inserted modules.
35