B Specifications - Omron C1000H Installation Manual

Sysmac series
Hide thumbs Also See for C1000H:
Table of Contents

Advertisement

Power Supply Model
Supply Voltage
Operating Voltage Range
Power Consumption
Output Capacity
24 VDC Output (see note 1)
Insulation Resistance
Dielectric Strength (see note 2)
Noise Immunity
Vibration Resistance
Shock resistance
Ambient Temperature
Ambient humidity
Atmosphere
Grounding
Degree of Protection
Weight
C1000H
C2000H Simplex
C2000H Duplex
Note 1. This output is not provided on PS223-E.
2. When performing the dielectric strength test or the insulation resistance test be sure to disconnect the
LG terminals from the GR (ground) terminals to protect the internal parts from damage.
Appendix B
Specifications
3G2A5-PS221-E/PS222-E/PS223-E
100 to 120/200 to 240 VAC (selectable)
50/60 Hz
85 to 132/170 to 264 VAC
150 VA max.
PS221-E: 7 A 5 VDC
PS223-E: 12 A 5 VDC
PS222-E: 7 A 5 VDC
0.8 A, 24 VDC 10%
5 MW min. (at 500 VDC) between AC terminals
1,500 VAC 50/60 Hz for 1 minute
(between AC and GR terminals) leakage
current 10 m A max.
1,000 Vp-p, pulse width: 1 ms, rise time: 1 ns
Mechanical durability: 10 to 25 Hz, 2 mm double amplitude, in X, Y, and Z
directions, for 2 hours each
Electrical durability: 16.7 Hz, 1 mm double amplitude, in X, Y, and Z directions, for
10 minutes each
2
98 m/s
each in X, Y, and Z direction, 3 times
Operating: 0°C to 55°C Storage: −20°C to 65°C
35% to 85% (without condensation)
Must be free from corrosive gasses
Less than 100 W
Mounted in a panel
8 kg max.
9 kg max.
10 kg max.
3G2A5-PS211-E/PS212-E,
C500-PS213-E
24 VDC
20.4 to 28.8 VDC
55 W max.
PS211-E: 7 A 5 VDC
PS213-E: 9 A 5 VDC
PS212-E: 7 A 5 VDC
Not provided
500 VAC 50/60 Hz for 1 minute
(between DC and GR terminals) leakage
current 1 mA max.
67

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

C2000h

Table of Contents