9. Multiple outdoor units control
System 4: Heating/Cooling system (with Boiler)
• Install a mixing tank (local supply) for connection of the boiler.
• Install a low loss header (local supply).
• Install booster heater between low loss header and mixing tank.
• For more details, refer to the installation manual of PAC-TH011HT-E.
14
15
13
12
Outdoor unit
16
19
20
18
17
Outdoor unit
21
No.
Component
1
Booster heater (local supply)
2
Circulation pump1 (local supply)
3
Flow switch1 (local supply) *2
4
Circulation pump2 (local supply)
5
Flow switch2 (local supply) *2
6
Flow temp. thermistor (THW1)
7
Return temp. thermistor (THW2)
8
Flow temp. thermistor (THW6) (option)
9
Return temp. thermistor (THW7) (option)
10 Boiler flow temp. thermistor (THWB1) (option)
*1 When the outdoor unit is split type, TH2 needs to be installed. <Fig. 9.2.1>
*2 For safety protection, it is recommended to install a flow switch.
System 5: Heating/Cooling system (with Hydrobox)*1
• Install a low loss header (local supply).
• Install booster heater toward the local system, relative to the low loss header.
Hydrobox
Outdoor unit
Hydrobox
Outdoor unit
<Fig. 9.2.7>
Boiler
1
6
2
7
3
Low loss header
(local supply)
<Fig. 9.2.6>
Wiring
Master Slave 1 Slave 2
Heating/
4
1
2
Cooling
5
3
Low loss header
(local supply)
10
8
Heating/Cooling
4
11
9
5
Mixing tank
(local supply)
No.
Component
11 Boiler return temp. thermistor (THWB2) (option)
12 Slave1 circulation pump1 (local supply)
13 Slave1 flow switch (local supply) *2
14 Slave1 flow temp. thermistor (THW1)
15 Slave1 return temp. thermistor (THW2)
16 Slave1 ref. liquid temp. thermistor (TH2) *1
17 Slave2 circulation pump1 (local supply)
18 Slave2 flow switch (local supply) *2
19 Slave2 flow temp. thermistor (THW1)
20 Slave2 return temp. thermistor (THW2)
21 Slave2 ref. liquid temp. thermistor (TH2) *1
No.
Component
1 Booster heater(local supply)
2 Circulation pump1 (local supply)
3 Flow switch1 (local supply) *2
4 Flow temp. thermistor (THW1)
5 Return temp. thermistor (THW2)
*1 Cooling system is available only with ERS models.
*2 For safety protection, it is recommended to install a flow switch.
Wiring
Master Slave 1 Slave 2
Wiring
Slave 1
Slave 2
Master
(Hydrobox)
(Hydrobox)
57