5. Dip Switch setting
5.2 Outdoor unit type
Set Dip SW 1-7 to set the outdoor unit type.
Dip SW 1-7
Setting
OFF
Split type
ON
Packaged type
Set Dip SW 1-2 to set the heat pump maximum outlet water temperature.
Dip SW 1-2
Setting
OFF
55°C
ON
60°C
When the outdoor unit is a SUHZ-SW series set the Dip SW1-2 to OFF, other than that, set the Dip SW 1-2 to ON.
Note: When Dip SW 1-2 is OFF (55°C) and an electric heater is not installed (*), 'Legionellla Prevention Mode' is NOT available.
* Dip SW settings set when no electric heater is installed.
Dip SW 1-2
Dip SW 1-4
OFF
OFF
OFF
OFF
5.3 Functions setting
Set Dip SW 1-1 to set whether the system has a boiler.
Dip SW 1-1
Setting
OFF
WITHOUT boiler
ON
WITH boiler
When Dip SW 1-1 is OFF, back-up operation of boiler is not available.
Set Dip SW 1-3 to set whether the system has a DHW tank.
Dip SW 1-3
Setting
OFF
WITHOUT DHW tank
ON
WITH DHW tank
When Dip SW 1-3 is OFF, DHW mode is not available.
Set Dip SW 1-4 to set whether the system has an immersion heater.
Dip SW 1-4
Setting
OFF
WITHOUT immersion heater
ON
WITH immersion heater
Set Dip SW 1-5 to set whether the system has a booster heater.
Dip SW 1-5
Setting
OFF
WITHOUT booster heater
ON
WITH booster heater
Set Dip SW 1-6 to set the booster heater function.
Dip SW 1-6
Setting
OFF
For heating only
ON
For heating and DHW
Set Dip SW 2-6 to set whether the system has a mixing tank.
Dip SW 2-6
Setting
OFF
WITHOUT mixing tank
ON
WITH mixing tank
When Dip SW 2-6 is OFF, back-up operation of boiler is not available.
When Dip SW 2-6 is OFF, 2-zone temperature control is not available.
Set Dip SW 2-7 to set activate or deactivate 2-zone temperature control.
Dip SW 2-7
Setting
OFF
Inactive
ON
Active
Set Dip SW 2-8 to set whether the system has a flow sensor.
Dip SW 2-8
Setting
OFF
WITHOUT flow sensor
ON
WITH flow sensor
28
Note
Necessary to connect TH2
Not necessary to connect TH2
Dip SW 1-5
Dip SW 1-6
ON
OFF
OFF
(ON/OFF)
Note
Not necessary to connect THW5
Necessary to connect THW5
Set Dip SW 3-4 to set whether the system has an electric energy meter.
Dip SW 3-4
Setting
OFF
WITHOUT electric energy meter
ON
WITH electric energy meter
Set Dip SW 3-6 to set activate or deactivate 2-zone valve ON/OFF control.
Dip SW 3-6
Setting
OFF
Inactive
ON
Active
Set Dip SW 3-7 to set type of the heat exchanger for DHW.
Dip SW 3-7
Setting
OFF
Coil in tank
ON
External plate HEX
Set Dip SW 3-8 to set whether the system has a heat meter.
Dip SW 3-8
Setting
OFF
WITHOUT heat meter
ON
WITH heat meter
Set Dip SW 4-1 to set activate or deactivate multiple units control.
Dip SW 4-1
Setting
OFF
Inactive
ON
Active
When Dip SW 4-1 is OFF, 2-zone temperature control and 2-zone valve ON/OFF
control is not available.
Set Dip SW 4-2 to set master or slave of multiple units control.
Dip SW 4-2
Setting
OFF
Slave
ON
Master
When multiple units control is not available, setting of Dip SW 4-2 is not necessary.
Set Dip SW 5-2 to set activate or deactivate advanced auto adaptation.
Dip SW 5-2
Setting
OFF
Inactive
ON
Active